Wash. Admin. Code § 51-11R-40213

Current through Register Vol. 24-23, December 1, 2024
Section 51-11R-40213 - Table R402.1.3-Insulation minimum R-values and fenestration requirements by components

TABLE R402.1.3

INSULATION MINIMUM R-VALUES AND FENESTRATION REQUIREMENTS BY COMPONENTSa

Climate Zone 5 and Marine 4

Fenestrationb,jU-Factor

0.30

SkylightbU-Factor

0.50

CeilingeR-Value

60

Wood Frame Wallg,iR-Value

20+5 or 13+10

Floor R-Value

30

Below-Grade Wallc,hR-Value

10/15/21 int + 5TB

Slabd,fR-Value and Depth

10, 4 ft.

For SI: 1 foot = 304.8 mm, ci = continuous insulation, int = intermediate framing.

aR-values are minimums. U-factors and SHGC are maximums. When insulation is installed in a cavity which is less than the label or design thickness of the insulation, the compressed R-value of the insulation from Appendix A Table A101.4 of chapter 51-11C WAC shall not be less than the R-value specified in the table.

b The fenestration U-factor column excludes skylights.

c "10/15/21+5TB" means R-10 continuous insulation on the exterior of the wall, or R-15 on the continuous insulation on the interior of the wall, or R-21 cavity insulation plus a thermal break between the slab and the basement wall at the interior of the basement wall. "10/15/21+5TB" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the wall. "TB" means R-5 thermal break between floor slab and basement wall.

d R-10 continuous insulation is required under heated slab on grade floors. See Section R402.2.9.1.

e For single rafter- or joist-vaulted ceilings, the insulation may be reduced to R-38 if the full insulation depth extends over the top plate of the exterior wall.

f R-7.5 continuous insulation installed over an existing slab is deemed to be equivalent to the required perimeter slab insulation when applied to existing slabs complying with Section R503.1.1. If foam plastic is used, it shall meet the requirements for thermal barriers protecting foam plastics.

g For log structures developed in compliance with Standard ICC 400, log walls shall meet the requirements for climate zone 5 of ICC 400.

h Int. (intermediate framing) denotes framing and insulation as described in Section A103.2.2 including standard framing 16 inches on center, 78 percent of the wall cavity insulated and headers insulated with a minimum of R-10 insulation.

i The first value is cavity insulation, the second value is continuous insulation. Therefore, as an example "13+10" means R-13 cavity insulation plus R-10 continuous insulation.

j A maximum U-factor of 0.32 shall apply to vertical fenestration products installed in buildings located above 4000 feet in elevation above sea level, or in windborne debris regions where protection of openings is required under Section R301.2.1.2 of the International Residential Code.

Wash. Admin. Code § 51-11R-40213

Amended by WSR 16-02-127, Filed 1/6/2016, effective 7/1/2016
Amended by WSR 20-01-047, Filed 12/9/2019, effective 7/1/2020
Amended by WSR 23-02-060, Filed 1/3/2023, effective 7/1/2023
Amended by WSR 24-03-084, Filed 1/16/2024, effective 3/15/2024

Statutory Authority: RCW 19.27A.020, 19.27A.045 and chapters 19.27 and 34.05 RCW. 13-04-055, § 51-11R-40213, filed 2/1/13, effective 7/1/13.