Wash. Admin. Code § 51-11R-40211

Current through Register Vol. 24-23, December 1, 2024
Section 51-11R-40211 - Table R40212-Insulation and fenestration requirements by component

TABLE R402.1.2 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa

CLIMATE ZONE 5 AND MARINE 4

Fenestration U-factorb

0.30

Skylight U-factor

0.50

Ceiling U-factor

0.024

Above-Grade Wall U-factor

0.056

Floor U-factor

0.029

Slab on Grade F-factor

0.54

Below Grade 2' Depth

Wall U-factor

0.042

Slab F-factor

0.59

Below Grade 3.5' Depth

Wall U-factor

0.040

Slab F-factor

0.56

Below Grade 7' Depth

Wall U-factor

0.035

Slab F-factor

0.50

aU-factors or F factors shall be obtained from measurement, calculation, or an approved source or as specified in Section R402.1.5.

b A maximumU -factor of 0.32 shall apply to vertical fenestration products installed in buildings located above 4000 feet in elevation above sea level, or in windborne debris regions where protection of openings is required under Section R301.2.1.2 of the International Residential Code.

Wash. Admin. Code § 51-11R-40211

Amended by WSR 16-02-127, Filed 1/6/2016, effective 7/1/2016
Amended by WSR 17-10-063, Filed 5/2/2017, effective 6/2/2017
Amended by WSR 20-01-047, Filed 12/9/2019, effective 7/1/2020
Amended by WSR 23-02-060, Filed 1/3/2023, effective 7/1/2023
Statutory Authority: RCW 19.27A.025, 19.27A.045, and 19.27.074. WSR 13-20-121, § 51-11R-40211, filed 10/1/13, effective 11/1/13. Statutory Authority: RCW 19.27A.020, 19.27A.045 and chapters 19.27 and 34.05 RCW. WSR 13-04-055, § 51-11R-40211, filed 2/1/13, effective 7/1/13. WSR 13-20-001, § 51-11R-40211, filed 9/18/2013, effective 10/19/2013