EXCEPTION: | Design flow rates exceeding the values in Table C403.3.7 are permitted in specific sections of pipe if the pipe is not in the critical circuit at design conditions and is not predicted to be in the critical circuit during more than 30 percent of operating hours. |
Table C403.3.7
Piping System Design Maximum Flow Rate in GPMa
Pipe Size | [LESS THAN EQUAL TO] 2000 hours/year | 2000 and [LESS THAN EQUAL TO] 4400 hours/year | 4400 hours/year | |||
(in) | Other | Variable Flow/ Variable Speed | Other | Variable Flow/ Variable Speed | Other | Variable Flow/ Variable Speed |
2 1/2 | 120 | 180 | 85 | 130 | 68 | 110 |
3 | 180 | 270 | 140 | 210 | 110 | 170 |
4 | 350 | 530 | 260 | 400 | 210 | 320 |
5 | 410 | 620 | 310 | 470 | 250 | 370 |
6 | 740 | 1100 | 570 | 860 | 440 | 680 |
8 | 1200 | 1800 | 900 | 1400 | 700 | 1100 |
10 | 1800 | 2700 | 1300 | 2000 | 1000 | 1600 |
12 | 2500 | 3800 | 1900 | 2900 | 1500 | 2300 |
Maximum velocity for pipes over 14 to 24 in. in size | 8.5 ft/s | 13.0 ft/s | 6.5 ft/s | 9.5 ft/s | 5.0 ft/s | 7.5 ft/s |
a There are no requirements for pipe sizes smaller than the minimum size or larger than the maximum size shown in the table.
Wash. Admin. Code § 51-11C-40337