Section 51-11C-40336 - Section C403.3.6-Ventilation for Group R-2 occupancyC403.3.6Ventilation for Group R-2 occupancy. For all Group R-2 dwelling and sleeping units, a balanced ventilation system with a heat recovery system shall provide outdoor air directly to all habitable spaces. The heat recovery system shall have a 60 percent minimum sensible recovery effectiveness as calculated in accordance with Section C403.3.5.1. The ventilation system shall allow for the design flow rates to be tested and verified at each habitable space as part of the commissioning process in accordance with Section C408.2.2. EXCEPTION: | Heat recovery and energy recovery ventilators (H/ERV) that are rated and listed in accordance with HVI 920 can demonstrate compliance with the sensible recovery effectiveness requirement using the adjusted sensible recovery effectiveness (ASRE) rating of the equipment at 32°F test conditions. Applied flow rate for ASRE rating shall be no less than the design flow rate or the closest value interpolated between two listed flow rates. |
Wash. Admin. Code § 51-11C-40336
Adopted by WSR 19-24-040, Filed 11/26/2019, effective 7/1/2020Amended by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023