Current through Public Act 156 of the 2024 Legislative Session
Section 290.649j - Delivery of gasoline; Stage I vapor-recovery system; applicability of subsection (7)(1) A person shall not deliver gasoline or permit the delivery of gasoline to a dispensing facility that lacks a stage I vapor-recovery system.(2) Prior to delivery of gasoline to a dispensing facility, a delivery vessel shall be certified by the department of environmental quality as vapor tight by meeting the requirements of R 336.1627 of the Michigan administrative code.(3) A person shall not deliver gasoline or permit the delivery of gasoline to a dispensing facility unless the stage I vapor-recovery system is employed during delivery and the dispensing facility storage tank is equipped with a permanent submerged fill pipe.(4) A stage I vapor-recovery system shall include a properly functioning interlocking system or procedure that ensures that the vapor-tight collection line is connected before any gasoline is loaded, or shall include an equivalent system approved by the department.(5) A stage I vapor-recovery system shall have a poppetted drybreak on the vapor return or an equivalent system approved by the department.(6) All open vent pipes for a stage I vapor-recovery system that are on stationary tanks at dispensing facilities shall be equipped with pressure-vacuum relief valves in a system approved by the department.(7) A dispensing facility regulated under this act is not subject to R 336.1606 or R 336.1703, or both, of the Michigan administrative code. This subsection does not apply to a delivery vessel which shall continue to be subject to the rules listed in this subsection.Amended by 2006, Act 104, s 9, eff. 4/6/2006.Add. 1993, Act 236, Imd. Eff. 11/13/1993.