Wis. Admin. Code Department of Safety and Professional Services SPS 321.25

Current through November 25, 2024
Section SPS 321.25 - Wood frame walls

Unless designed through structural analysis, wood frame walls shall comply with the following requirements.

(1) STUD CONFIGURATION. Wood studs shall comply with the size and spacing requirements indicated in Table 321.25-A. Studs in the exterior walls shall be placed with the wide faces perpendicular to the plane of the wall.

Note: See ch. SPS 325 Appendix A for acceptable nailing schedule.

Note: See s. SPS 321.10 for requirements on treating wood for decay and termite resistance.

(2) TOP PLATES.
(a)General. Except as allowed under subd. 3., top plates shall be provided and configured as follows:
1. Studs at bearing walls shall be capped with double top plates.
2. End joints in double top plates shall be offset at least 2 stud spaces.
3. Double top plates shall be overlapped at the corners and at intersections of partitions.
4. The plate immediately above the stud may have a joint only when directly over the stud.
(b)Notching and boring.
1. When piping or ductwork is placed in an exterior wall or an interior load-bearing wall, such that at least half of the top plate is removed, the plate shall be reinforced with a steel angle at least 2 inches by 2 inches by 20 gauge thick.

Note: 20 gauge is approximately 0.036 inch.

2. The steel angle shall span the gap and extend at least to the midpoint of the adjacent stud spaces.
3. Other equivalent materials may be used in accordance with s. SPS 321.02.
(c)Exceptions.
1. A single top plate may be used in place of a double top plate provided a rafter is located directly over the studs and the plate is securely tied at the end joints, corners and intersecting walls. Joints may occur in single top plates only when directly over a stud.
2. A continuous header, consisting of two 2-inch members set on edge, may be used in lieu of a double plate if tied to the adjacent wall.
(2m) BOTTOM PLATES.
(a)Masonry foundation walls with open top course.
1. Where a masonry foundation wall has an open top course, a bottom plate at least as wide as the foundation wall shall be fastened to the foundation.
2. Where anchor bolts are used on a masonry foundation wall with an open top course, the minimum width of an individual piece making up the bottom plate shall be at least 5 1/2 inches.

Note: A sill plate can be made of multiple pieces to achieve the full width.

(b)Extension beyond the bearing surface. All of the following requirements apply to a sawn-lumber sill plate with uniform loading that is partially extended beyond the load-bearing surface of a foundation wall in order to put the exterior surface of an upper-lying wall flush with or beyond the exterior surface of insulation which is placed on the outside of the foundation wall:
1. The center of any anchor bolt shall be set back from the side edge of the sill plate by a distance of at least 4 times the diameter of the bolt.
2. The thickness of the concrete or mortar cover around any anchor bolt shall comply with ACI 318 Section 7.7.

Note: Under ACI 318 Section 7.7, the minimum cover for a 5/8-inch-diameter or smaller bolt is 1 1/2 inches.

3. Where a stud wall bears directly on a double bottom plate, the plate may not extend more than 1 1/2 inches beyond the load-bearing surface of the foundation wall.
4. Where a stud wall bears directly on a single bottom plate, the plate may not extend more than 1 inch beyond the load-bearing surface of the foundation wall.
(3) WALL OPENINGS.
(am)Headers. Where doors or windows occur, headers shall be used to carry the load across the opening.
(bm)Header size. The size of headers shall be determined in accordance with the spans and loading conditions listed in Tables 321.25 -B, 321.25-C and 321.25-D. Headers for longer spans shall be designed by an engineering method under s. SPS 321.02.
(cm)Header support. Headers in bearing walls shall be supported in accordance with subd. 1. or 2. or 3.
1. Headers 3 feet or less in length shall be directly supported on each end by either:
a. The single common stud and a shoulder stud; or
b. The single common stud with a framing anchor attached.
2. Headers greater than 3 feet but less than or equal to 6 feet in length shall be directly supported on each end by the single common stud and a shoulder stud.
3. Headers greater than 6 feet in length shall be directly supported on each end by the single common stud and 2 shoulder studs.
(4) NOTCHING. Notching and boring of columns or posts is prohibited unless designed through structural analysis. Studs shall not be cut or bored more than 1/3 the depth of the stud, unless the stud is reinforced.
(5) PARTITIONS. Load-bearing partitions shall be placed over beams, girders, or other load-bearing partitions. Load-bearing partitions running at right angles to the joists shall not be offset from the main girder or walls more than the depth of the joist unless the joists are designed to carry the load.
(6) POSTS AND COLUMNS.
(a)General.
1. Posts and columns shall be installed to resist imposed loads.
2. Posts and columns shall bear directly over the middle 1/3 of a footing.
3. Posts and columns shall be restrained at the top and bottom to resist displacement.
4. All columns shall be positively attached to the beams they support using clips, straps or saddles.
5. Posts and columns that use a height adjustment mechanism shall have the mechanism imbedded in concrete or permanently disabled after installation.
(b)Bearing surface. Posts and columns shall have a steel bearing plate affixed to one or both ends to distribute any applied loads and to prevent fiber crushing of any structural member being supported.
(c)Steel posts or columns. Steel posts or columns shall be sized according to one of the following methods:
1. Manufactured columns shall follow the manufacturer's testing and listing.

Table 321.25-A

SIZE, HEIGHT AND SPACING OF WOOD STUDSa,c

Bearing and Exterior Nonbearing Walls

Interior Nonbearing Walls

Nominal Stud

Size

(inches)

Maximum

Laterally

Unsupported

Stud Heighta

(feet)

Maximum

Spacing When Supporting Roof and Ceiling Only (inches)

Maximum

Spacing When

Supporting

One Floor,

Roof and

Ceiling

(inches)

Maximum

Spacing When

Supporting

Two Floors,

Roof and

Ceiling

(inches)

Maximum Spacing When Supporting One Floor Only (inches)

Maximum Laterally Unsupported Stud Heighta (feet)

Maximum Spacing (inches)

Click to view image

Click to view image

Click to view image

Click to view image

2 x 3b

-

-

-

-

-

10

16

2 x 4

10

24

16

-

24

14

24

3 x 4

10

24

24

16

24

14

24

2 x 5

10

24

24

-

24

16

24

2 x 6

12d

24

24

16

24

20

24

aListed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted where justified by analysis. Studs shall be stud grade or better, except that utility grade may be used when spaced not more than 16 inches on center, supports no more than a roof and ceiling and does not exceed 8 feet in height for exterior walls or 10 feet in height for interior nonload-bearing walls.

bMay not be used in exterior walls.

cAll spacing dimensions are to the center of the studs.

dUse of stud heights that range from over 10 feet to 12 feet for bearing and exterior nonbearing walls is prohibited unless supported by structural analysis. The allowable deflection may not exceed whichever of the following are applicable:

Interior walls and partitions - span height/180.

Exterior walls with plaster or stucco finish - span height/360.

Exterior walls with other brittle finishes - span height/240.

Exterior walls with flexible finishes - span height/120.

Exterior walls with interior gypsum wallboard finish - span height/180.

Any manufacturer-specified limits for any included windows or doors.

Note: A 3-story frame house with walls constructed of 2 x 4 standard grade studs would require a 12-inch stud spacing on the lowest level, a 24-inch stud spacing on the intermediate level, and a 24-inch stud spacing on the upper level.

2. Columns made solely of steel pipe stock shall follow Table 321.25-E.
3. Columns made of steel stock, not meeting the requirements of subd. 1. or 2., shall follow a nationally accepted design specification or the size shall be determined through structural analysis or load testing.
(d)Wood posts or columns. Wood posts or columns shall be sized according to Table 321.25-F or the size shall be determined through structural analysis or load testing.

Table 321.25-B

ALLOWABLE SPANS (FEET) FOR HEADERS SUPPORTING ROOF/CEILING ASSEMBLIES*

Header Members

House Width (feet)

Two 2 x 4s

Two 2 x 6s

Two 2 x 8s

Two 2 x 10s

Two 2 x 12s

Zone 2/Zone 1

Zone 2/Zone 1

Zone 2/Zone 1

Zone2/Zone 1

Zone 2/Zone 1

24

2.5

2.5

4

4

5

5

7

6

9

8

26

2.5

2

4

3

5

5

7

6

8

7

28

2.5

2

4

3

5

4

6

6

8

7

30

2.5

2

4

3

5

4

6

6

8

7

32

2

2

3

3

5

4

6

5

7

7

Table 321.25-C

ALLOWABLE SPANS (FEET) FOR HEADERS SUPPORTING ONE FLOOR*

Header Members

House Width (feet)

Two 2 x 4s

Two 2 x 6s

Two 2 x 8s

Two 2 x 10s

Two 2 x 12s

24

2.5

4

5

6

8

26

2.5

3

5

6

8

28

2

3

5

6

7

30

2

3

4

6

7

32

2

3

4

5

7

Table 321.25-D

ALLOWABLE SPANS (FEET) FOR HEADERS SUPPORTING ONE FLOOR AND ROOF/CEILING ASSEMBLY*

Header Members

House Width (feet)

Two 2 x 4s

Two 2 x 6s

Two 2 x 8s

Two 2 x 10s

Two 2 x 12s

Zone 2/Zone 1

Zone 2/Zone 1

Zone 2/Zone 1

Zone2/Zone 1

Zone 2/Zone 1

24

1.5

1.5

3

2.5

4

3

5

4

6

5

26

1.5

1.5

2.5

2.5

3

3

4

4

5

5

28

1.5

1.5

2.5

2.5

3

3

4

4

5

5

30

1.5

1.5

2.5

2.5

3

3

4

4

5

5

32

1.5

1.5

2.5

2

3

3

4

4

5

5

*These tables are based on wood with a fiber bending stress of 1,000 psi. For other species with different fiber bending stresses, multiply the span by the square root of the ratio of the actual bending stress to 1,000 psi. Example: From Table 321.25-B, the allowable roof/ceiling span for a 28-foot wide house in zone 2, using two 2 x 8 header members with a 1400 psi bending stress, is 5 feet x [SQUARE ROOT] 71400/1000 = 5.9 feet.

Table 321.25-E

COLUMNS MADE OF STEEL PIPE STOCK1,2

Column Diameter (inches)

Wall

Thickness

(inches)

Weight/ft (pounds)

Height (feet)

Allowable

Load (pounds)

3

0.216

7.58

8

34,000

10

28,000

12

22,000

3.5

0.226

9.11

8

44,000

10

38,000

12

32,000

4

0.237

10.79

8

54,000

10

49,000

12

43,000

5

0.258

14.62

8

78,000

10

73,000

12

68,000

6

0.280

18.97

8

106,000

10

101,000

12

95,000

1This Table is based on a yield strength or Fy of 36,000 psi.

2This table is for columns made solely of steel pipe stock. The addition of any adjustment mechanism or other feature will alter the load-carrying capacity of the column.

Table 321.25-F

WOOD COLUMNS

Wood

Nominal Size

(inches)

Cross Section

Area

(inches)

Height (feet)

Allowable Load (pounds)

4 x 4

12.25

8

4,900

10

3,100

12

2,150

4 x 6

19.25

8

7,700

10

4,900

12

3,400

6 x 6

30.25

8

30,000

10

18,900

12

13,300

Note: This Table is based on a modulus of elasticity or E of 1,000,000 psi and a fiber bending strength or Fb of 1,000 psi.

(7) FOUNDATION CRIPPLE WALLS.
(a) Foundation cripple walls shall be framed with studs at least as large as the studs above.
(b) When more than 4 feet in height, cripple walls shall be framed with studs needed for an additional floor level.
(c) Cripple walls with a stud height of less than 14 inches shall be sheathed on at least one side for its entire length with a wood structural panel that is fastened to both the top and bottom plates or the cripple walls shall be constructed of solid blocking.
(d) Cripple walls with a stud height of 14 inches or greater shall be braced in accordance with sub. (8).
(e) Cripple walls shall be fully supported by a continuous foundation.
(8) WALL BRACING.
(a)General. Dwellings using wood-framed walls shall be braced in accordance with this section. Where a building, or a portion thereof, does not comply with one or more of the bracing requirements in this section, those portions shall be designed and constructed in accordance with accepted engineering practice.

Note: Acceptable engineering wall bracing practices include any of the following:

1. The provisions under section R602.10 or R602.12 of the International Residential Code (IRC) - 2012.
2. Design in accordance with the engineering basis of the 2012 IRC bracing provisions, such as described in Crandell, J. and Martin, Z., "The Story Behind the 2009 IRC Wall Bracing Provisions (Part 2: New Wind Bracing Requirements)," Wood Design Focus, Forest Products Society, Peachtree Corners, GA, Spring 2009.
3. Installation instructions from the manufacturer of the bracing product that are compliant with s. SPS 321.02.

Note: For a walk-out basement where some of the walls are concrete and other walls or portions thereof are wood-framed, the Department considers a minimum 8-inch-nominal-thickness poured-in-place concrete basement wall as being equivalent in lateral load and shear resistance to any of the allowable wood-framed wall bracing materials. To determine the required bracing for a walk-out basement, first draw a rectangle around the entire floor plan and projections as if all of the walls are wood-framed. Determine the required bracing amounts per the chosen bracing material and method and then locate the bracing to meet the requirements of Figure 321.25-C. Any required braced wall panel locations that occur on a wall or portion of a wall that is actually of poured-in-place concrete construction is considered equivalent, and that amount of bracing will count towards the minimum required amount and will not need to be provided in another location on that rectangle side.

(b)Bracing Materials and Methods. Wall bracing shall consist of the materials and methods listed in Table 321.25-G or approved alternatives capable of providing the required wind load resistance as determined in accordance with s. SPS 321.02(1) (c).

Table 321.25-G

BRACING METHODSa, f

Material

Minimum Brace Material Thickness or Size

Maximum

Nominal Wall

Heightb

Minimum Braced Wall

Panel Width or Brace

Angle

Connection Criteria

Minimum Fasteners

Maximum Spacing

Intermittent Bracing Methods

LIBc Let-in bracing

1x4 wood brace

(or approved metal brace installed per manufacturer instructions)

10'

45° angle and maximum 16" o.c. stud spacingb

2-8d common nails or 3-8d

box nails (2 3/8" long x 0.113" diameter)

Per stud and top and bottom platese

DWB

Diagonal wood boards

3/4" (1" nominal) for maximum 24" o.c. stud spacing

10'

48"

2-8d box nails (2 3/8" long x 0.113" diameter) or 2 - 1 3/4" long 16-gage staples

Per stud and top and bottom platese

WSP

Wood structural panel

3/8" for maximum 16"o.c. stud spacing;

7/16" for maximum 24" o.c. stud spacing

10'

48"

6d common nail or 8d box nail (2 3/8" long x 0.113" diameter); or 7/16"- or 1/2"-crown 16-gage staples, 1 1/4" long

6" edges, 12" field (nails)

3" edges, 6" field (staples)

SFB

Structural fiber-board sheathing

1/2" for maximum 16" o.c. stud spacing

10'

48"

1 1/2" long x 0.120" diameter galvanized roofing nails or 1"-crown 16-gage staples, 1 1/4" long

3" edges, 6" field

GB

Gypsum board

(installed on both sides of wall)

1/2" for maximum 24" o.c. stud spacing

10'

96"

5d cooler nails, or #6 screws

7" edges, 7" field

(including top and bottom plates)

Continuous Sheathed Bracing Methods

CS-WSPd

Continuous sheathed WSP

3/8" for maximum 16"o.c. stud spacing;

7/16" for maximum 24" o.c. stud spacing

12'

Refer to Table 321.25-H

Same as WSP

Same as WSP

CS-SFBd

Continuous sheathed SFB

1/2" for maximum 16" o.c. stud spacing

Same as SFB

Same as SFB

Narrow Panel Bracing

PF Portal frame

7/16"

12'

Refer to Figure 321.25-A

Refer to Figure 321.25-A

Refer to Figure 321.25-A

aThe interior side of all exterior walls shall be sheathed with minimum 1/2-inch gypsum wallboard unless otherwise permitted to be excluded by this subsection. All edges of panel-type wall bracing, except horizontal joints in GB bracing, shall be attached to framing or blocking.

bThe actual measured wall height shall include stud height and thickness of top and bottom plates. The actual wall height shall be permitted to exceed the listed nominal values by not more than 41/2 inches. Tabulated bracing amounts in s. SPS 321.25(8) (c) are based on a 10-foot nominal wall height for all bracing methods and shall be permitted to be adjusted to other nominal wall heights not exceeding 12 feet in accordance with footnotes to Table 321.25-I or Table 321.25-J.

cLIB is not permitted for walls supporting a roof and two floors. Two LIB braces installed at a 60° angle from horizontal shall be permitted to be substituted for each 45°angle LIB brace.

dBracing with CS-WSP and CS-SFB shall have sheathing installed on all sheathable surfaces above, below, and between wall openings.

dShall be attached to the top and bottom plates and any intermediate studs, in one continuous length.

eEach braced panel may contain no more than one hole, having a maximum dimension of no more than ten percent of the least dimension of the panel, and confined to the middle three-fourths of the panel.

Table 321.25-Ha, b

MINIMUM WIDTHS OF CS-WSP AND CS-SFB BRACED WALL PANELS

Maximum Opening Height Adjacent to Braced Wall Panel

Minimum Width of Full-Height Braced Wall Panel (inches)

8' Tall Wall

9' Tall Wall

10' Tall Wall

12' Tall Wall

5'- 4"

24

27

30

36

6'- 8"

32

30

30

36

8'

48

41

38

36

9'

-

54

46

41

10'

-

-

60

48

12'

-

-

-

72

aSheathing shall extend from the top of the top plate to the bottom of the bottom plate and may be multiple sheets. All joints shall be blocked.

bInterpolation is permitted.

Figure 321.25-A

METHOD PF - PORTAL FRAME BRACE CONSTRUCTION

Click to view image

Note: Steel headers are permitted if designed by structural analysis.

Note: As shown in the above cross-section, 1/2-inch gypsum wallboard is not required on the interior side of the wall.

(c)Bracing amount. Bracing methods and materials complying with Table 321.25-G shall be applied to walls in accordance with all of the following requirements:
1. For the purpose of determining bracing amounts, the outermost extents of the building plan at each floor level shall be circumscribed with a rectangle to define the overall length of each building side as shown in Figure 321.25-B.
2. In no case may the amount of bracing be less than two braced wall panels on walls parallel to each rectangle side for each floor level of the building.
3. Where used, the number of intermittent brace panels applied to walls parallel to each rectangle side shall comply with Table 321.25-I.
4. Where used, the total length of continuous sheathed brace panels applied to walls parallel to each building side shall comply with Table 321.25-J.
5. The location of brace panels applied to walls parallel to each building side shall comply with Figure 321.25-C.
6. Balloon-frame walls may be no longer than 21 feet and shall have a maximum height of two floors unless constructed in accordance with an approved design. Wall framing shall be continuous from the lowest floor to the wall top plate at the roof. All edges of sheathing shall be supported on and fastened to blocking or framing. Braced wall panels may not be required on the balloon-frame wall portion provided the bracing amount and brace spacing requirement are satisfied for the building side. Where brace panels are located on the balloon-frame wall portion, they shall have a height-to-width ratio of not more than 2.5:1.
7. For a gable end wall, if the brace-panel height does not exceed 12 feet at the highest portion and if the 121/2-foot and 21-foot spacing requirements in Figure 321.25-C are met, the wall is adequately braced. Where a brace panel exceeds 12 feet in height, it shall have a height-to-width ratio of not more than 2.5:1, and comply with Figure 21.25-C.

FIGURE 321.25-B

DEFINING BUILDING SIDES AND LENGTHS WITH ONE OR MORE CIRCUMSCRIBED RECTANGLESa,b,c

Click to view image

(1)Basic floor plan

Click to view image

(2)Angled-building-side pland

Click to view image

(3)Angled floor plane

Click to view image

TABLE 321.25-I

REQUIRED NUMBER OF INTERMITTENT BRACED WALL PANELS ON WALLS PARALLEL TO EACH RECTANGLE SIDE AT EACH FLOOR LEVELa,b,c,d,e,f, h, j

Wall Supporting:

Required Number of Brace Panels on a Building Side

Length of Perpendicular Side (feet)g

<=25

<=50

<=75

Roof and ceiling only

Click to view image

1i

2

3

One floor, roof and ceiling

Click to view image

2

4

6

Two floors, roof and ceiling

Click to view image

3

6

9

aInterpolation is permitted. Extrapolation to buildings larger than addressed in this table is prohibited.

bThis table applies to wind exposure category B. For wind exposure category C or D, multiply the number of braced wall panels required by 1.3 or 1.6, respectively.

Wind exposure category B is comprised of urban and suburban areas, wooded areas, or other terrain with numerous closely spaced obstructions having the size of single-family dwellings or larger. Exposure B shall be assumed unless the site meets the definition of another type exposure.

Wind exposure category C is comprised of flat, open country and grasslands with scattered obstructions, including surface undulations or other irregularities, having heights generally less than 30 feet extending more than 1,500 feet from the building site in any quadrant. This exposure also applies to any building located within Exposure B type terrain where the building is directly adjacent to open areas of Exposure C type terrain in any quadrant for a distance of more than 600 feet.

Wind exposure category D is comprised of flat, unobstructed areas exposed to wind flowing over open water for a distance of at least 1 mile. This exposure applies only to those buildings and other structures exposed to the wind coming from over the water. Exposure D extends inland from the shoreline a distance of 1,500 feet or 10 times the height of the building or structure, whichever is greater.

cTabulated values are based on a nominal wall height of 10 feet. For nominal wall heights other than 10 feet and not more than 12 feet, multiply the required number of brace panels by the following factors: 0.9 for 8 feet, 0.95 for 9 feet, 1.15 for 11 feet, or 1.3 for 12 feet.

dTabulated values are based on a roof with a top-of-wall-to-ridge height of 10 feet. For top-of-wall-to-ridge heights other than 10 feet, multiply the required number of brace panels by the following factors for each floor level support condition:

Roof only - 0.7 for 5 feet, 1.3 for 15 feet, or 1.6 for 20 feet

Roof + 1 Floor - 0.85 for 5 feet, 1.15 for 15 feet, or 1.3 for 20 feet

Roof + 2 Floors - 0.9 for 5 feet or 1.1 for 15 feet.

eWhere minimum 1/2-inch gypsum wallboard is not included on the interior side of the wall, multiply the number of braced wall panels by 1.7 for LIB bracing or 1.4 for all other bracing methods, except this increase is not required for the portal frame method.

fAdjustments in footnotes b to e apply cumulatively. Fractions of panels shall be rounded to the nearest one-half braced wall panel.

gPerpendicular sides to the front and rear sides are the left and right sides. Perpendicular sides to the left and right sides are the front and rear sides. See Figure 321.25-B.

hThe following braced wall panel conditions shall be permitted to be counted as one-half a braced wall panel toward meeting the required number of panels:

(1) one 60 degree LIB;
(2) one 48" GB or one 96" GB with gypsum wallboard on one side;
(3) one 36" WSP or SFB braced wall panel for wall heights not more than 9 feet;
(4) a 48" WSP or SFB braced wall panel where there is no more than one unblocked horizontal joint; or
(5) one PF brace panel complying with Figure 321.25-A.

iThis value of less than 2 serves only as the beginning value for calculation purposes. The resulting value shall be 2 or greater, to be consistent with subd. 2.

jAny floor, habitable or otherwise, that is contained wholly within the roof rafters or roof trusses is exempt from being considered a floor for purposes of determining wall bracing if the top-of-wall-to-ridge height does not exceed 20 feet and if no opening in the roof exceeds 48 inches in height.

Table 321.25-J

REQUIRED LENGTH OF CONTINUOUS BRACING ON WALLS PARALLEL TO EACH RECTANGLE SIDE AT EACH FLOOR LEVEL a,b,c,d,e,g,h, j

Top-of-Wall-to-Ridge Height (feet)

Wall Supporting:

Total Required Length (feet) of Full-Height Bracing on Any Side of Rectangle

Length of Perpendicular Side (feet)f

10

20

30

40

50

60

70

80

Roof and ceiling only

See Image

2.0 i

3.5 i

5.0

6.0

7.5

9.0

10.5

12.0

10

One floor, roof and ceiling

See Image

3.5 i

6.5

9.0

12.0

14.5

17.0

19.8

22.6

Two floors, roof and ceiling

See Image

5.0

9.5

13.5

17.5

21.5

25.5

29.2

33.4

Roof and ceiling only

See Image

2.6 i

4.6

6.5

7.8

9.8

11.7

13.7

15.7

15

One floor, roof and ceiling

See Image

4.0

7.5

10.4

13.8

16.7

19.6

22.9

26.2

Two floors, roof and ceiling

See Image

5.5

10.5

14.9

19.3

23.7

27.5

32.1

36.7

Roof and ceiling only

See Image

2.9 i

5.2

7.3

8.8

11.1

13.2

15.4

17.6

20

One floor, roof and ceiling

See Image

4.5

8.5

11.8

15.6

18.9

22.1

25.8

29.5

Two floors, roof and ceiling

See Image

6.2

11.9

16.8

21.8

27.3

31.1

36.3

41.5

aInterpolation is permitted. Extrapolation to buildings larger than addressed in this table is prohibited.

bThis table applies to wind exposure category B. For wind exposure category C or D, multiply the required length of wall bracing by 1.3 or 1.6, respectively. Wind exposure categories are as defined in Table 321.25-I footnote b.

cTabulated values are based on a nominal wall height of 10 feet. For nominal wall heights other than 10 feet, multiply the required length of bracing by the following factors: 0.90 for 8 feet, 0.95 for 9 feet, 1.05 for 11 feet, or 1.10 for 12 feet.

dWhere minimum 1/2-inch gypsum wallboard interior finish is not provided, the required bracing amount for the affected rectangle side shall be multiplied by 1.4, except this increase is not required for the portal frame method.

eAdjustments in footnotes b to d apply cumulatively.

fPerpendicular sides to the front and rear sides are the left and right sides. Perpendicular sides to the left and right sides are the front and rear sides. See Figure 321.25-B.

gContinuous sheathing shall be applied to all surfaces of the wall, including areas between brace panels and above and below wall openings.

hWhen used on a wall line with continuous sheathing, each portal frame panel is counted for its actual length in contributing toward the length of continuous sheathing used on other portions of the same wall line, such as the building side at a given story level.

iAny value of less than 4.0 in this table serves only as the beginning value for calculation purposes. The resulting value shall be 4.0 or greater, to be consistent with Table 321.25-H and subd.2.

jAny floor, habitable or otherwise, that is contained wholly within the roof rafters or roof trusses is exempt from being considered a floor for purposes of determining wall bracing if the top-of-wall-to-ridge height does not exceed 20 feet and if no opening in the roof exceeds 48 inches in height.

Figure 321.25-C

LOCATION OF BRACED WALL PANELS ALONG A BUILDING SIDEa

Click to view image

(d)Braced wall panel support. Braced wall panels shall be supported on floor framing or foundations as follows:
1. Where joists are perpendicular to braced wall lines above or below, blocking shall be provided between the joists at braced wall panel locations to permit fastening of wall plates in accordance with the fastener table in the ch. SPS 325 Appendix A.
2. Where joists are parallel to braced wall lines above or below, a rim joist or other parallel framing member shall be provided at the wall to permit fastening of wall plates in accordance with the fastener table in the ch. SPS 325 Appendix A.
3. Braced wall panels shall be permitted to be supported on cantilevered floor joists meeting the cantilever limits of s. SPS 321.22(6) provided joists are blocked at the nearest bearing wall location, except such blocking is not required for cantilevers not exceeding 24 inches where a full height rim joist is provided.

Wis. Admin. Code Department of Safety and Professional Services SPS 321.25

Cr. Register, November, 1979, No. 287, eff. 6-1-80; cr. (1) (d) and am. (3) (b), Register, February, 1985, No. 350, eff. 3-1-85; r. and recr. (3) (b), am. Table 21.25 B and E, Register, January, 1989, No. 397, eff. 2-1-89; am. (3) (a) and (6), Register, March, 1992, No. 435, eff. 4-1-92; r. and recr. (1) (c), am. Table 21.25-D, cr. Table 21.25-F, Register, November, 1995, No. 479, eff. 12-1-95; am. Table 21.25-A, Register, January, 1999, No. 517, eff. 2-1-99; r. (1) (b) and (c), renum. (1) (d) to be (b), r. and recr. (2), (6) and Tables 21.25 -E and F, and am. (3) (b) 3., Register, March, 2001, No. 543, eff. 4-1-01; CR 02-077: r. (3) (c) Register May 2003 No. 569, eff. 8-1-03; CR 08-043: am. (1) (title), r. (1) (b), renum. (1) (a) and (6) (a) 4. to be (1) and (6) (a) 5., r. and recr. Table 21.25-A, cr. (6) (a) 4., (7), (8) and (9) Register March 2009 No. 639, eff. 4-1-09; correction in Figure 21.25-E made under s. 13.92(4) (b) 7, Stats., Register March 2009 No. 639; CR 09-104: am. 21.25 (8) (e) 2., Table 21.25-H, (9) (b) 3., Table 21.25-J, Figure 21.25-G (c), (9) (c) 4. Register December 2010 No. 660, eff. 1-1-11; correction in (1), (2) (b) 3., (3) (a), (6) (c) 2., (d), (8) (c) 1. d., 2. c., (d), (e) 2., 3., (f) 2., (g) 3., (h) 2. b., (9) (b) 1., 2. b., d., 4. b., c., i., (c) 2. (intro.), b., c., d., 3., 4., 5. a., c., d., g., h., i., Table 321.25-H, Figure 321.25-F, -H to -K made under s. 13.92(4) (b) 7, Stats., Register December 2011 No. 672; EmR1403: emerg. am. Table 321.25-A, (7) (d), r. and recr. (8) (b), (c), Tables 321.25 -G to 321.25-J, Figures 321.25-A to 321.25-C, r. (8) (d) to (f), renum. (8) (g) (title), (intro.), 1. to 3. to (8) (d) (title), (intro.), 1. to 3., r. (8) (g) 4., (h), (9), Tables 321.25 -K, 321.25-L, Figures 321.25-D to 321.25-K, eff. 4-1-14; CR 14-015: am. Table 321.25-A, (7) (d), r. and recr. (8) (b), (c), Tables 321.25 -G to 321.25-J, Figures 321.25-A to 321.25-C, r. (8) (d) to (f), renum. (8) (g) (title), (intro.), 1. to 3. to (8) (d) (title), (intro.), 1. to 3., r. (8) (g) 4., (h), (9), Tables 321.25 -K, 321.25-L, Figures 321.25-D to 321.25-K Register August 2014 No. 704, eff. 9-1-14.
Amended by, CR 15-041: cr. (2m), renum. (3) (intro.), (a), (b) to (3) (am), (bm), (cm), cr. (3) (am) (title), am Table I (title), Table J (title) Register December 2015 No. 720, eff. 1-1-16; CR 15-043: am. (8) (d) 1., 2. Register December 2015 No. 720, eff.1/1/2016