Current through Register Vol. 24-21, November 1, 2024
Section 51-54A-0308 - Open flames308.1.7Religious ceremonies. Participants in religious ceremonies shall not be precluded from carrying hand-held candles. See RCW 19.27.031(3). 308.1.7.1Aisles and exits. Candles shall be prohibited in areas where occupants stand, or in an aisle or exit. EXCEPTION: | Candles used in religious ceremonies. |
308.1.9Decorative open flame tables. Gas-fired portable or fixed open flame fire tables and fireplaces are required to be provided with approved protection devices to prevent occupants from using flame, and from flame being exposed to combustible material. A fire extinguisher shall be located within 75 feet of travel distance or as approved. Where located indoors, the supply gas valve shall be interlocked with building fire alarm and/or fire sprinklers, where provided.Wash. Admin. Code § 51-54A-0308
Amended by WSR 16-03-055, Filed 1/16/2016, effective 7/1/2016Amended by WSR 21-04-003, Filed 1/20/2021, effective 2/20/2021Amended by WSR 22-13-093, Filed 6/14/2022, effective 7/1/2023Statutory Authority: RCW 19.27A.031, 19.27.074 and chapters 19.27 and 34.05 RCW. 13-04-063, § 51-54A-0308, filed 2/1/13, effective 7/1/13.