C408.7 Refrigeration system commissioning. All installed refrigeration systems subject to Section C410 shall be included in the commissioning process required by Section C408.1.
EXCEPTIONS: | 1. Self-contained refrigeration systems are exempt from the commissioning process. 2. Total installed capacity for refrigeration is equal to or less than 240 kBtu/h. |
C408.7.1 System testing. Functional performance testing shall demonstrate that compressors, heat exchangers, piping, distribution systems, and system-to-system interfacing relationships are installed and operate in accordance with approved construction documents. Testing shall include the sequence of operation and be conducted under full-load at, part-load and the following conditions:
Wash. Admin. Code § 51-11C-40807