Section 51-11C-40505 - Section C405.4-Interior lighting power requirements

C405.4 Interior lighting power requirements . A building complies with this section if its total connected interior lighting power calculated under Section C405.4.1 is no greater than the interior lighting power allowance calculated under Section C405.4.2.