Table C404.3.1 Piping Volume and Maximum Piping Lengths
Nominal Pipe Size (inches) | Volume (liquid ounces per foot length) | Maximum Piping Length (feet) | |
Public lavatory faucets | Other fixtures and appliances | ||
1/4 | 0.33 | 6 | 50 |
5/16 | 0.5 | 4 | 50 |
3/8 | 0.75 | 3 | 50 |
1/2 | 1.5 | 8 | 43 |
5/8 | 2 | 8 | 32 |
3/4 | 3 | 0.5 | 21 |
7/8 | 4 | 0.5 | 16 |
1 | 5 | 0.5 | 13 |
1 1/4 | 8 | 0.5 | 8 |
1 1/2 | 11 | 0.5 | 6 |
2 or larger | 18 | 0.5 | 4 |
The volume from the nearest source of heated water to the termination of the fixture supply pipe shall be as follows:
Table C404.3.2.1 Internal Volume of Various Water Distribution Tubing
Ounces of Water per Foot of Tube | |||||||||
Nominal Size (inches) | Copper Type M | Copper Type L | Copper Type K | CPVC CTS SDR 11 S11 | CPVC 40 | CPVC 80 | PE-RT SDR | Composite ASTM F1281 | PEX CTS SDR 9 |
3/8 | 1.06 | 0.97 | 0.84 | N/A | 1.17 | - | 0.64 | 0.63 | 0.64 |
1/2 | 1.69 | 1.55 | 1.45 | 1.25 | 1.89 | 1.46 | 1.18 | 1.31 | 1.18 |
3/4 | 3.43 | 3.22 | 2.90 | 2.67 | 3.38 | 2.74 | 2.35 | 3.39 | 2.35 |
1 | 5.81 | 5.49 | 5.17 | 4.43 | 5.53 | 4.57 | 3.91 | 5.56 | 3.91 |
11/4 | 8.70 | 8.36 | 8.09 | 6.61 | 9.66 | 8.24 | 5.81 | 8.49 | 5.81 |
11/2 | 12.18 | 11.83 | 11.45 | 9.22 | 13.20 | 11.38 | 8.09 | 13.88 | 8.09 |
2 | 21.08 | 20.58 | 20.04 | 15.79 | 21.88 | 19.11 | 13.86 | 21.48 | 13.86 |
Wash. Admin. Code § 51-11C-40403