EXCEPTION: | Heat rejection devices where energy usage is included in the equipment efficiency ratings listed in Tables C403.3.2(1), C403.3.2(2), C403.3.2(3), C403.3.2(4), C403.3.2(8), C403.3.2(9), C403.3.2(10) and C403.3.2(16). |
Heat rejection equipment shall have a minimum efficiency performance not less than values specified in Table C403.3.2 (7).
EXCEPTIONS: | 1.Fans serving multiple refrigerant or fluid cooling circuits. 2.Condenser fans serving flooded condensers. |
The required heat recovery system shall have the capacity to provide the smaller of:
EXCEPTIONS: | 1. Facilities that employ condenser heat recovery for space heating or reheat purposes with a heat recovery design exceeding 30 percent of the peak water-cooled condenser load at design conditions. 2. Facilities that provide 60 percent of their service water heating from site recovered energy. |
Buildings using off-site generated steam where the condensate is not returned to the source, shall have an on-site condensate water heat recovery system.
EXCEPTION: | Systems complying with Section C403.3.5, Dedicated outdoor air systems. |
EXCEPTIONS: | 1. Where energy recovery systems are restricted by Section 514 of the International Mechanical Code to sensible energy, those systems shall not be included in the calculation of total building exhaust airflow. 2. Exhaust air systems handling contaminated airstreams that are regulated by applicable codes or accreditation standards and pose a health risk to maintenance personnel to maintain heat recovery devices, those systems shall not be included in the calculation of total building exhaust airflow. |
Wash. Admin. Code § 51-11C-4039