EXCEPTIONS: | 1. Spaces including, but not limited to, dining areas, where more than 75 percent of the space design outdoor airflow is transfer air required for makeup air supplying an adjacent commercial kitchen. 2. Spaces with one of the following occupancy classifications as defined in Table 403.3.1.1 of the International Mechanical Code : Correctional cells, educational laboratories, barbers, beauty and nail salons, and bowling alley seating. 3. Dormitory sleeping areas with fewer than five occupants per space. 4. Spaces with ventilation not provided by a single-zone system where the design occupant component outdoor airflow is less than 100 cfm (23.6 L/s), or 200 cfm (47.2 L/s) with system having energy recovery with minimum 60 percent sensible effectiveness. Design occupant component outdoor airflow shall be calculated as the product of the design number of occupants in the space and the people outdoor airflow rate per occupant ( Rp) as established in Table 403.3.1.1 of the International Mechanical Code. 5. Spaces with ventilation not provided by a single-zone system where the total system design outdoor airflow is less than 750 cfm (354 L/s), or 1500 cfm (708 L/s) with system having energy recovery with minimum 60 percent sensible effectiveness. |
EXCEPTION: | These system types may use other means of adjusting outdoor air: 1. Single zone systems designed to recirculate return air. 2. Systems with total supply air less than 1500 cfm (708 L/s). |
Wash. Admin. Code § 51-11C-40371