C403.5.1 Integrated economizer control. Economizer systems shall be integrated with the mechanical cooling system and be configured to provide partial cooling even where additional mechanical cooling is required to provide the remainder of the cooling load. Controls shall not be capable of creating a false load in the mechanical cooling system by limiting or disabling the economizer or any other means, such as hot gas bypass, except at the lowest stage of mechanical cooling.
Units that include an air economizer shall comply with the following:
Table C403.5.1 DX Cooling Stage Requirements for Modulating Airflow Units
Rating Capacity | Minimum Number of Mechanical Cooling Stages | Minimum Compressor Displacementa |
> 65,000 Btu/h and < 240,000 Btu/h | 3 stages | < 35% of full load |
>240,000 Btu/h | 4 stages | < 25% full load |
For SI: 1 British thermal unit per hour = 0.2931 W.
aFor mechanical cooling stage control that does not use variable compressor displacement, the percent displacement shall be equivalent to the mechanical cooling capacity reduction evaluated at the full load rating conditions for the compressor.
Wash. Admin. Code § 51-11C-40351