EXCEPTION: | These concentration limits do not apply where 50 percent or more of the boiler system capacity serves Group R-2 occupancies. |
Table C403.3.4.3
Boiler Stack-Gas Oxygen Concentrations
Boiler System Type | Maximum Stack-Gas Oxygen Concentrationa |
Less than 10% of the boiler system capacity is used for process applications at design conditions | 5% |
All others | 3% |
a Concentration levels measured by volume on a dry basis over firing rates of 20 to 100 percent.
The system turndown requirement shall be met through the use of multiple single input boilers, one or more modulating boilers or a combination of single input and modulating boilers.
Table C403.3.4.4
Boiler Turndown
Boiler System Design Input (Btu/h) | Minimum Turndown Ratio |
[GREATER THAN EQUAL TO] 1,000,000 and less than or equal to 5,000,000 | 3 to 1 |
[GREATER THAN EQUAL TO] 5,000,000 and less than or equal to 10,000,000 | 4 to 1 |
[GREATER THAN EQUAL TO] 10,000,000 | 5 to 1 |
EXCEPTIONS: | 1. Where 25 percent of the annual space heating requirement is provided by site-recovered energy, or heat recovery chillers. 2. Space heating boilers installed in individual dwelling units. 3. Where 50 percent or more of the design heat load is served using perimeter convective heating, radiant ceiling panels, or both. 4. Individual gas boilers with input capacity less than 300,000 Btu/h shall not be included in the calculations of the total system input or total system efficiency. |
Wash. Admin. Code § 51-11C-40334