Section 51-11C-403328 - Table C403.3.2(8)-Electrically operated variable refrigerant flow air conditioners-Minimum efficiency requirements

Table C403.3.2(8)

Electrically Operated Variable Refrigerant Flow Air Conditioners-Minimum Efficiency Requirementsb

Equipment Type

Size Category

Heating Section Type

Subcategory or Rating Condition

Minimum Efficiency

Test Procedurea

VRF Air Conditioners, Air Cooled

< 65,000 Btu/h

All

VRF Multi-Split System

13.0 SEER

AHRI 1230

[GREATER THAN EQUAL TO] 65,000 Btu/h and < 135,000 Btu/h

Electric Resistance (or none)

VRF Multi-Split System

11.2 EER

15.5 IEER

[GREATER THAN EQUAL TO] 135,000 Btu/h and < 240,000 Btu/h

Electric Resistance (or none)

VRF Multi-Split System

11.0 EER

14.9 IEER

[GREATER THAN EQUAL TO] 240,000 Btu/h

Electric Resistance (or none)

VRF Multi-Split System

10.0 EER

13.9 IEER

For SI: 1 British thermal unit per hour = 0.2931 W.

a Chapter 6 contains a complete specification of the referenced standards, which include test procedures, including the reference year version of the test procedure.

b This table is a replica of ASHRAE 90.1 Table 6.8.1-8 Electrically Operated Variable-Refrigerant-Flow Air Conditioners-Minimum Efficiency Requirements.