For buildings with a total equipment cooling capacity of 300 tons and above, the equipment shall comply with one of the following:
EXCEPTIONS: | 1. Where the designer demonstrates that the water quality at the building site fails to meet manufacturer's specifications for the use of water-cooled equipment. 2. Air-cooled chillers with minimum efficiencies at least 10 percent higher than those listed in Table C403.3.2(3). 3. Replacement of existing air-cooled chiller equipment. 4. Air-to-water heat pump units that are configured to provide both heating and cooling and that are rated in accordance with AHRI 550/590. |
The FLadj and PLVadj values are applicable only for centrifugal chillers meeting all of the following full-load design ranges:
* 36.00°F [LESS THAN EQUAL TO] LvgEvap [LESS THAN EQUAL TO] 60.00°F
* LvgCond [LESS THAN EQUAL TO] 115.00°F
* 20.00°F [LESS THAN EQUAL TO] LIFT [LESS THAN EQUAL TO] 80.00°F
Manufacturers shall calculate the FLadj and PLVadj before determining whether to label the chiller. Centrifugal chillers designed to operate outside of these ranges are not covered by this code.
EXCEPTION: | Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities. |
EXCEPTIONS: | 1. Health care facilities licensed by the state where chapter 246-320 or 246-330 WAC requires steam injection humidifiers in duct work downstream of final filters. 2. Systems with water economizer. 3. 100 percent outside air systems with no provisions for air recirculation to the central supply fan. 4. Nonadiabatic humidifiers cumulatively serving no more than 10 percent of a building's air economizer capacity as measured in cfm. This refers to the system cfm serving rooms with stand alone or duct mounted humidifiers. |