Wash. Admin. Code § 296-876-60040

Current through Register Vol. 24-23, December 1, 2024
Section 296-876-60040 - Clearances
(1) You must make sure ladders without wells or cages are at least thirty inches from the nearest permanent object on the climbing side, measured perpendicular to the ladder from the centerline of the rungs, cleats, or steps.

EXEMPTION:

When unavoidable obstructions are encountered, the minimum perpendicular clearance between the center-line of the rungs, cleats, or steps and an obstruction on the climbing side may be reduced to twenty-four inches if a deflection device is installed to guide persons around the obstruction.

(2) You must make sure ladders without wells or cages have a clear width from the nearest permanent object on each side of the ladder of at least fifteen inches, measured from the center of the rungs, cleats, or steps.
(3) You must make sure the distance from the centerline of the rungs, cleats, or steps to the nearest permanent object in back of the ladder is at least seven inches.

EXEMPTION:

Fixed ladders in elevator pits may reduce the minimum clearance from the ladder to the nearest permanent object in back of the ladder to four and one-half inches.

Click to view image

Figure D-5 - Fixed Ladder Clearances

Wash. Admin. Code § 296-876-60040

Amended by WSR 14-09-095, filed 4/22/14, effective 7/1/2014
Amended by WSR 20-09-146, Filed 4/21/2020, effective 10/1/2020

Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 06-16-020, § 296-876-60040, filed 7/24/06, effective 12/1/06.