Note: | If possible, reverse the platform controls to free a platform that is caught, snagged, or otherwise prevented from normal motion by an adjacent structure or other obstacle. |
Table 6
Minimum Safe Approach Distance
Voltage | Minimum Safe Approach Distance |
Less than 300 volts (insulated lines) | 3 feet (0.9 m) |
Less than 300 volts (uninsulated lines) | 10 feet (3.1 m) |
300 volts to 50 kv | 10 feet (3.1 m) |
More than 50 kv | 10 feet (3.1 m) + 0.4 inches (1.0 cm) for each 1 kv over 50 kv |
Wash. Admin. Code § 296-869-60035
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 06-19-073, § 296-869-60035, filed 9/19/06, effective 1/1/07.