Note: | This section establishes minimal levels of lighting for safety purposes only. Guidelines pertaining to optimal levels of lighting and illumination may be found in Practice for Industrial Lighting, ANSI/IES RP7-1979. (See the resource section of this book on how to contact ANSI.) |
Lighting Table | ||
Activity | Minimum acceptable average lighting level in an area:(Foot-candles) | Any one single measurement used to determine the average lighting level* cannot be less than:(Foot-candles) |
Indoor task | 10 | 5 |
Outdoor task | 5 | 2.5 |
Nontask activities for both indoor and outdoor | 3 | 1.5 |
* Lighting levels must be measured at thirty inches above the floor/working surface at the task.
Note: | * Lighting levels can be measured with a light meter. * Conversion information: 1 foot-candle = 1 lumen incident per square foot = 10.76 lux. |
Wash. Admin. Code § 296-800-21005