Wash. Admin. Code § 296-45-48550

Current through Register Vol. 24-23, December 1, 2024
Section 296-45-48550 - Turbine generators
(1) Smoking and other ignition sources are prohibited near hydrogen or hydrogen sealing systems, and signs warning of the danger of explosion and fire must be posted.
(2) Excessive hydrogen makeup or abnormal loss of pressure must be considered as an emergency and shall be corrected immediately.
(3) A sufficient quantity of inert gas must be available to purge the hydrogen from the largest generator.

Wash. Admin. Code § 296-45-48550

Amended by WSR 19-13-083, Filed 6/18/2019, effective 8/1/2019

Statutory Authority: RCW 49.17.010, [49.17].040, [49.17].050 and [49.17].060. 98-07-009, § 296-45-48550, filed 3/6/98, effective 5/6/98.