This section applies to work on exposed live parts, or near enough to them, to expose the employee to any hazard they present.
Notes: | *One qualified electrical employee will serve principally as a standby person who must be so located that they may physically reach the other qualified electrical employee in the event of an accident either with their hand or with a hot stick twelve feet or less in length. The standby person will be so positioned as to be able to observe the other employee, their bodily movements, and verbally warn of any impending dangers. In no case when working in pairs will qualified electrical employees work simultaneously on energized wires or parts of different phases or polarity; *When installing or removing a hot line clamp connection on a multiphase system, it is permissible for the second qualified electrical employee to stand by at the lower controls of the aerial lift provided the connection or disconnection does not interrupt or pick up the load. The hot line clamp and connecting jumper must be constructed so it cannot make contact with any other energized parts. The work must not be performed above lines or apparatus energized at more than 600 V. *In cases of necessity the standby person may temporarily assist the other qualified electrical employee provided that they both work on wires or parts of the same phase or polarity. Both qualified electrical employees must so position themselves so that the presence of the second person does not increase the hazard. |
Notes: | * The hot line clamp and connecting jumper must be constructed so that it cannot make contact with any other energized parts. |
* On a multiphase feed this applies only when one single-phase line or apparatus is present on the load side. |
Table 2
AC Live Work Minimum Approach Distance
Distance to Employee | ||||||
Voltage in Kilovolts Phase-to-Phase | Phase-to-Ground | Phase-to-Phase | ||||
(ft-in) | (ft-1/10) | (m) | (ft-in) | (ft-1/10) | (m) | |
Table 2-A For Voltages of 72.5 KV and Less (1, 2, 3, 4) | ||||||
0 to 0.050 | not specified | not specified | ||||
0.051 to 0.300 | avoid contact | avoid contact | ||||
0.301 to 0.750 | 1'-2" | 1.09 | 0.33 | 1'-2" | 1.09 | 0.33 |
0.751 to 5 | 2'-1" | 2.07 | 0.63 | 2'-1" | 2.07 | 0.63 |
5.1 to 15.0 | 2'-2" | 2.14 | 0.65 | 2'-3" | 2.24 | 0.68 |
15.1 to 36.0 | 2'-7" | 2.53 | 0.77 | 3'-0" | 2.92 | 0.89 |
36.1 to 46.0 | 2'-10" | 2.76 | 0.84 | 3'-3" | 3.22 | 0.98 |
46.1 to 72.5 | 3'-3" | 3.29 | 1.00 | 4'-0" | 3.94 | 1.20 |
1Employers may use the minimum approach distances in this table provided the worksite is at an elevation of 3, 000 feet (900 meters) or less. If employees will be working at elevations greater than 3, 000 feet (900 meters) above mean sea level, the employer must determine minimum approach distances by multiplying the distances in this table by the correction factor in Table 3 below, altitude correction factors. | ||||||
2For single-phase systems, use voltage-to-ground. | ||||||
3For single-phase lines off three phase systems, use the phase-to-phase voltage of the system. | ||||||
4The 46.1 to 72.5 kV phase-to-ground 3-3 distance contains a 1-3 electrical component and a 2'-0 inadvertent movement component. | ||||||
Table 2-B For Voltages of 72.6 KV andup 5, 6, 7) | Phase-to-Ground | Phase-to-Phase | ||||
(ft-in) | (ft-1/10) | (m) | (ft-in) | (ft-1/10) | (m) | |
72.6 to 121 | 3'-9"** | 3.71** | 1.13 | 4'-8" | 4.66 | 1.42 |
121.1 to 145.0 | 4'-4" | 4.27 | 1.30 | 5'-5" | 5.38 | 1.64 |
145.1 to 169.0 | 4'-10" | 4.79 | 1.46 | 6'-5" | 6.36 | 1.94 |
169.1 to 242.0 | 6'-8" | 6.59 | 2.01 | 10'-2" | 10.10 | 3.08 |
242.1 to 362.0 | 11'-3" | 11.19 | 3.41 | 18'-2" | 18.11 | 5.52 |
362.1 to 420.0 | 14'-0" | 13.94 | 4.25 | 22'-5" | 22.34 | 6.81 |
420.1 to 550.0 | 16'-8" | 16.63 | 5.07 | 27'-1" | 27.03 | 8.24 |
550.1 to 800.0 | 22'-7" | 22.57 | 6.88 | 37'-5" | 37.34 | 11.38 |
5Employers may use the minimum approach distances in this table provided the worksite is at an elevation of 3, 000 feet (900 meters) or less. If employees will be working at elevations greater than 3, 000 feet (900 meters) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table 3 below, altitude corrections factor. | ||||||
6Employers may use the phase-to-phase minimum approach distances in this table provided that no insulated tool spans the gap and no large conductive object is in the gap. (See Equation 1 for voltages of 72.6-800 kV in Appendix A.) | ||||||
7The 72.6 to 121 kV phase-to-ground 3-9 distance contains a 2-9 electrical component and a 1'-0 inadvertent movement component.** | ||||||
Note: The clear live-line tool distance shall equal or exceed the values for the indicated voltage ranges. |
Table 3 - Altitude Correction Factors
Altitude above sea level (m)
A | |
0 to 900 .......................... | 1.00 |
901 to 1, 200 ....................... | 1.02 |
1, 201 to 1, 500 ..................... | 1.05 |
1, 501 to 1, 800 ..................... | 1.08 |
1, 801 to 2, 100 ..................... | 1.11 |
2, 101 to 2, 400 ..................... | 1.14 |
2, 401 to 2, 700 ..................... | 1.17 |
2, 701 to 3, 000 ..................... | 1.20 |
3, 001 to 3, 600 ..................... | 1.25 |
3, 601 to 4, 200 ..................... | 1.30 |
4, 201 to 4, 800 ..................... | 1.35 |
4, 801 to 5, 400 ..................... | 1.39 |
5, 401 to 6, 000 ..................... | 1.44 |
Table 4 Assumed Maximum Per-Unit Transient Overvoltage
Voltage Range (kV) | Type of Current (ac or dc) | Assumed Maximum Per-Unit Transient Over-voltage |
72.6 to 420.0 | ac | 3.5 |
420.1 to 550.0 | ac | 3.0 |
550.1 to 800.0 | ac | 2.5 |
250 to 750 | dc | 1.8 |
Notes: | *WAC 296-45-475(5)(a) and 296-45-48525(1) contain requirements for the guarding and isolation of live parts. Parts of electric circuits that meet these two provisions are not considered as "exposed" unless a guard is removed or an employee enters the space intended to provide isolation from the live parts. *When an employee is required to work on or within reach of any unprotected conductors that are or may become energized at more than 50 volts and less than 600 volts between phases, they shall take the following precautions: -They shall wear approved insulating gloves or insulating gloves and sleeves during the time they are working on such conductor; or -They shall cover, with approved devices, any adjacent unprotected conductor that could be touched by any part of their body, and use insulated tools. -Cables which are properly insulated for the voltages to which they are energized, shall be considered as an effective barrier to protect the employees and Table 2 need not apply. *Appendix A of this chapter contains additional information relating to working on exposed energized parts. |
Notes: | *Appendix D of this chapter provides guidance on estimating available heat energy. The department will deem employers following the guidance in Appendix D to be in compliance with (b) of this subsection. An employer may choose a method of calculating incident heat energy not included in Appendix D if the chosen method reasonably predicts the incident energy to which the employee would be exposed. *This subsection does not require the employer to estimate the incident heat energy exposure for every job task performed by each employee. The employer may make broad estimates that cover multiple system areas provided the employer uses reasonable assumptions about the energy-exposure distribution throughout the system and provided the estimates represent the maximum employee exposure for those areas. For example, the employer could estimate the heat energy just outside a substation feeding a radial distribution system and use that estimate for all jobs performed on that radial system. |
Note: | This subsection prohibits clothing made from acetate, nylon, polyester, rayon and polypropylene, either alone or in blends, unless the employer demonstrates that the fabric has been treated to withstand the conditions that may be encountered by the employee or that the employee wears the clothing in such a manner as to eliminate the hazard involved. |
Note: | This subsection does not apply to conductors that are capable of carrying, without failure, the maximum available fault current for the time the circuit protective devices take to interrupt the fault. |
Note: | See Appendix D of this chapter for further information on the selection of appropriate protection. |
Wash. Admin. Code § 296-45-325
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 05-17-038, § 296-45-325, filed 8/9/05, effective 10/1/05; 03-17-071, § 296-45-325, filed 8/19/03, effective 11/1/03. Statutory Authority: RCW 49.17.040. 99-09-080, § 296-45-325, filed 4/20/99, effective 8/1/99. Statutory Authority: RCW 49.17.010, [49.17].040, [49.17].050 and[49.17].060 . 98-07-009, § 296-45-325, filed 3/6/98, effective 5/6/98.