Current through Register Vol. 24-21, November 1, 2024
Section 296-45-305 - Live-line tools(1) Design of tools. Live-line tool rods, tubes, and poles must be designed and constructed to withstand the following minimum tests:(a) 100, 000 volts per foot (3281 volts per centimeter) of length for 5 minutes if the tool is made of fiberglass-reinforced plastic (FRP); or(b) 75, 000 volts per foot (2461 volts per centimeter) of length for 3 minutes if the tool is made of wood; or(c) Other tests that the employer can demonstrate are equivalent. Note: | Live-line tools using rod and tube that meet ASTM F711-02 (2013), Standard Specification for Fiberglass-Reinforced Plastic (FRP) Rod and Tube Used in Live-Line Tools, conform to subsection (1)(a) of this section. |
(2) Condition of tools. (a) Each live-line tool must be wiped clean and visually inspected for defects before use each day.(b) If any defect or contamination that could adversely affect the insulating qualities or mechanical integrity of the live-line tool is present after wiping, the tool must be removed from service and examined and tested according to this section before being returned to service.(c) Live-line tools used for primary employee protection must be removed from service every two years and whenever required under this section for examination, cleaning, repair, and testing as follows:(i) Each tool must be thoroughly examined for defects.(ii) If a defect or contamination that could adversely affect the insulating qualities or mechanical integrity of the live-line tool is found, the tool must be repaired and refinished or must be permanently removed from service. If no such defect or contamination is found, the tool must be cleaned and waxed.(iii) The tool must be tested in accordance with this section under the following conditions: (A) After the tool has been repaired or refinished; and(B) After the examination if repair or refinishing is not performed, unless the tool is made of FRP rod or foam-filled FRP tube and the employer can demonstrate that the tool has no defects that could cause it to fail in use.(iv) The test method used must be designed to verify the tool's integrity along its entire working length and, if the tool is made of fiberglass-reinforced plastic, its integrity under wet conditions.(v) The voltage applied during the tests must be as follows:(A) 75, 000 volts per foot (2461 volts per centimeter) of length for one minute if the tool is made of fiberglass; or(B) 50, 000 volts per foot (1640 volts per centimeter) of length for one minute if the tool is made of wood; or(C) Other tests that the employer can demonstrate are equivalent. Note: | Guidelines for the examination, cleaning, repairing, and in-service testing of live-line tools are contained in the Institute of Electrical and Electronics Engineers Guide for In-Service Maintenance and Electrical Testing of Live-Line Tools, IEEE Std. 516-2009. |
(d) Live-line tools and rope must be stored and maintained and used in such a manner as to prevent damage. Live-line tools and ropes must not be used for purposes other than line work.Wash. Admin. Code § 296-45-305
Amended by WSR 16-10-082, Filed 5/3/2016, effective 7/1/2016Amended by WSR 19-13-083, Filed 6/18/2019, effective 8/1/2019Statutory Authority: RCW 49.17.010, [49.17].040, [49.17].050 and [49.17].060. 98-07-009, § 296-45-305, filed 3/6/98, effective 5/6/98.