Note: Personal protective equipment requirements are contained in chapter 296-24 WAC Part L, and WAC 296-800-160.
Note: Rubber insulating equipment meeting the following national consensus standards is deemed to be in compliance with subsection (1) of this section:
American Society for Testing and Materials (ASTM) D 120-87, Specification for Rubber Insulating Gloves.
ASTM D 178-93, Specification for Rubber Insulating Matting.
ASTM D 1048-93, Specification for Rubber Insulating Blankets.
ASTM D 1049-93, Specification for Rubber Insulating Covers.
ASTM D 1050-90, Specification for Rubber Insulating Line Hose.
ASTM D 1051-87, Specification for Rubber Insulating Sleeves.
These standards contain specifications for conducting the various tests required in subsection (1) of this section. For example, the a-c and d-c proof-tests, the breakdown test, the water soak procedure, and the ozone test mentioned in this paragraph are described in detail in the ASTM standards.
Note: Standard electrical test methods considered as meeting this requirement are given in the following national consensus standards:
American Society for Testing and Materials (ASTM) D 120-87, Specification for Rubber Insulating Gloves. ASTM D 1048-93, Specification for Rubber Insulating Blankets.
ASTM D 1049-93, Specification for Rubber Insulating Covers. ASTM D 1050-90, Specification for Rubber Insulating Line Hose.
ASTM D 1051-87, Specification for Rubber Insulating Sleeves.
Table A-2. - A-C Proof-Test Requirements Maximum proof-test current, mA (gloves only) Class of equipment | Proof-test voltage rms V | 267-mm (10.5-in) glove | 356-mm (14-in) glove | 406-mm (16-in) glove | 457-mm (18-in) glove |
0 | 5,000 | 8 | 12 | 14 | 16 |
1 | 10,000 | 14 | 16 | 18 | |
2 | 20,000 | 16 | 18 | 20 | |
3 | 30,000 | 18 | 20 | 22 | |
4 | 40,000 | 22 | 24 |
Table A-3. -D-C Proof-Test Requirements | Class of equipment | Proof-test voltage |
0 | 20,000 | |
1 | 40,000 | |
2 | 50,000 | |
3 | 60,000 | |
4 | 70,000 |
ASTM F 478-92, Specification for In-Service Care of Insulating Line Hose and Covers.
ASTM F 479-88a, Specification for In-Service Care of Insulating Blankets.
ASTM F 496-93b, Specification for In-Service Care of Insulating Gloves and Sleeves.
Note: Marking of equipment and entering the results of the tests and the dates of testing onto logs are two acceptable means of meeting this requirement.
Note: The d-c voltages listed in this table are not appropriate for proof-testing rubber insulating line hose or covers. For this equipment, d-c proof-tests must use a voltage high enough to indicate that the equipment can be safely used at the voltages listed in Table A-4. See ASTM D 1050-90 and ASTM D 1049-88 for further information on proof-tests for rubber insulating line hose and covers.
Table A-4. -Glove Tests-Water Level1,2 Class of glove | mm. | A-C proof-test in. | mm. | D-C proof-test in. |
0 | 38 | 1.5 | 38 | 1.5 |
1 | 38 | 1.5 | 51 | 2.0 |
2 | 64 | 2.5 | 76 | 3.0 |
3 | 89 | 3.5 | 102 | 4.0 |
4 | 127 | 5.0 | 153 | 6.0 |
1 The water level is given as the clearance from the cuff of the glove to the water line, with a tolerance of 13 mm. (0.5 in.).
2 If atmospheric conditions make the specified clearances impractical, the clearances may be increased by a maximum of 25 mm. (1 in.).
Table A-5. -Rubber Insulating Equipment Voltage Requirements Class of equipment | Maximum use voltage1 a-c-rms | Retest volt-age2 a-c-rms | Retest volt-age2 d-c-rms |
0 | 1,000 | 5,000 | 20,000 |
1 | 7,500 | 10,000 | 40,000 |
2 | 17,000 | 20,000 | 50,000 |
3 | 26,500 | 30,000 | 60,000 |
4 | 36,000 | 40,000 | 70,000 |
Note: You must only use rubber gloves on voltages of 5000 volts phase-to-phase or less.
1The maximum use voltage is the a-c voltage (rms) classification of the protective equipment that designates the maximum nominal design/voltage of the energized system that may be safely worked. The nominal design voltage is equal to the phase-to-phase voltage on multiphase circuits. However, the phase-to-ground potential is considered to be the nominal design/voltage:
2 You must apply the proof-test voltage continuously for at least one minute, but no more than three minutes.
Table A-6. -Rubber Insulating Equipment Test Intervals | Type of equipment | When to test |
Rubber insulating line hose | Upon indication that insulating value is suspect. | |
Rubber insulating covers | Upon indication that insulating value is suspect. | |
Rubber insulating blankets | Before first issue and every 12 months thereafter.1 | |
Rubber insulating gloves | Before first issue and every 6 months there-after.1 | |
Rubber insulating sleeves | Before first issue and every 12 months thereafter.1 |
1 If the insulating equipment has been electrically tested but not issued for service, it may not be placed into service unless it has been electrically tested within the previous 12 months.
Wash. Admin. Code § 296-24-980
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 04-18-080, § 296-24-980, filed 8/31/04, effective 11/1/04. Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. 01-11-038, § 296-24-980, filed 5/9/01, effective 9/1/01. Statutory Authority: Chapter 49.17 RCW. 91-24-017 (Order 91-07), § 296-24-980, filed 11/22/91, effective 12/24/91.