Note: Suitability of equipment for an identified purpose may be evidenced by listing or labeling for that identified purpose.
Note: Wooden plugs driven into holes in masonry, concrete, plaster, or similar materials are not considered secure means of fastening electric equipment.
Table S-1-Minimum Depth of Clear Working Space at Electric Equipment, 600 V or Less
Nominal voltage to ground | Minimum clear distance for condition2, 3 | ||
Condition A | Condition B | Condition C | |
ft | ft | ft | |
0 - 150 | 13.0 | 13.0 | 3.0 |
151 - 600 | 13.01 | 3.5 | 4.0 |
Notes to Table S-1:
1 Minimum clear distances may be 2 feet 6 inches for installations built before April 16, 1981.
2 Conditions A, B, and C are as follows:
Condition A-Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides effectively guarded by suitable wood or other insulating material.
Insulated wire or insulated busbars operating at not over 300 volts are not considered live parts.
Condition B-Exposed live parts on one side and grounded parts on the other side.
Condition C-Exposed live parts on both sides of the work space (not guarded as provided in Condition A) with the operator between.
3 Working space is not required in back of assemblies such as dead-front switchboards or motor control centers where there are no renewable or adjustable parts (such as fuses or switches) on the back and where all connections are accessible from locations other than the back. Where rear access is required to work on deenergized parts on the back of enclosed equipment, you must provide a minimum working space of 30 inches horizontally.
Note: A dropped, suspended, or similar ceiling that does not add strength to the building structure is not considered a structural ceiling.
Note: Piping and other facilities are not considered foreign if provided for fire protection of the electrical installation.
Table S-2-Minimum Depth of Clear Working Space at Electric Equipment, Over 600 V
Nominal voltage to ground | Minimum clear distance for condition2, 3 | ||
Condition A | Condition B | Condition C | |
ft | ft | ft | |
601-2500 V | 3.0 | 4.0 | 5.0 |
2501-9000 V | 4.0 | 5.0 | 6.0 |
9001 V-25 kV | 5.0 | 6.0 | 9.0 |
Over 25-75 kV1 | 6.0 | 8.0 | 10.0 |
Above 75 kV1 | 8.0 | 10.0 | 12.0 |
Notes to Table S-2:
1 Minimum depth of clear working space in front of electric equipment with a nominal voltage to ground above 25,000 volts may be the same as that for 25,000 volts under Conditions A, B, and C for installations built before April 16, 1981.
2 Conditions A, B, and C are as follows:
Condition A-Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides effectively guarded by suitable wood or other insulating material. Insulated wire or insulated busbars operating at not over 300 volts are not considered live parts.
Condition B-Exposed live parts on one side and grounded parts on the other side. Concrete, brick, and tile walls are considered as grounded surfaces.
Condition C-Exposed live parts on both sides of the work space (not guarded as provided in Condition A) with the operator between.
3 Working space is not required in back of equipment such as dead-front switchboards or control assemblies that has no renewable or adjustable parts (such as fuses or switches) on the back and where all connections are accessible from locations other than the back. Where rear access is required to work on deenergized parts on the back of enclosed equipment, you must provide a minimum working space of 30 inches horizontally.
Table S-3-Elevation of Unguarded Live Parts Above Working Space
Nominal voltage between phases | Elevation |
ft | |
601-7500 V | 19.0 |
7501 V-35 kV | 9.0 |
Over 35 kV | 9.0 + 0.37 in/kV over 35 kV |
1 The minimum elevation may be 8 feet 6 inches for installations built before August 13, 2007. The minimum elevation may be 8 feet for installations built before April 16, 1981, if the nominal voltage between phases is in the range of 601-6600 volts.
Wash. Admin. Code § 296-24-95703
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060, and chapter 49.17 RCW. 12-16-064, § 296-24-95703, filed 7/31/12, effective 9/1/12.