TABLE H-32
Minimum design pressure of container lb. per sq. in. gage | |||
Container type | For gases with vapor press. Not to exceed lb. per sq. in. gage at 100°F. (37.8°C.) | 1949 and earlier editions of ASME Code (Par. U-68, U-69) | 1949 edition of ASME Code (Par. U-200, 1U-201); 1950, 1952, 1956, 1959, 1962, 1965, and 1968 (Division I) editions of ASME Code; All editions of API-ASME Code2 |
2001 | 215 | 200 | 250 |
1 Container type may be increased by increments of 25. The minimum design pressure of containers must be 100% of the container type designation when constructed under 1949 or earlier editions of the ASME Code (Par. U-68 and U-69). The minimum design pressure of containers must be 125% of the container type designation when constructed under: (1) The 1949 ASME Code (Par. U-200 and U-201), (2) 1950, 1952, 1956, 1959, 1962, 1965, and 1968 (Division I) editions of the ASME Code, and (3) all editions of the API-ASME Code.
2 Construction of containers under the API-ASME Code is not authorized after July 1, 1961.
Wash. Admin. Code § 296-24-47511
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 04-19-051, § 296-24-47511, filed 9/14/04, effective 2/1/05. Statutory Authority: RCW 49.17.010,[49.17].040 and [49.17].050. 99-17-094, § 296-24-47511, filed 8/17/99, effective 12/1/99; Order 73-5, § 296-24-47511, filed 5/9/73 and Order 73-4, § 296-24-47511, filed 5/7/73.