Except as provided in WAC 296-24-47505(10)(n), you must not locate the discharge from safety relief devices less than 3 feet horizontally away from any building opening which is below the level of such discharge and it must not terminate beneath any building unless such space is well ventilated to the outside and is not enclosed on more than two sides.
The provisions of (f) of this subsection apply except that you must not leave containers having a water capacity greater than 2 1/2 pounds (nominal one pound LP-gas capacity) unattended in such buildings.
Note: This provision is not to be construed as requiring an automatic changeover device.
TABLE H-30
Regulatory delivery pressure | Relief valve start to discharge pressure setting (percent of regulator deliver pressure) | |
Minimum | Maximum | |
1 p.s.i.g. or less ______ | 200 | 300 |
Above 1 p.s.i.g. but not over 3 p.s.i.g. _________ | 140 | 200 |
Above 3 p.s.i.g. ______ | 125 | 200 |
Permissible product. You must not place a product in a container marked with a service pressure less than four-fifths of the maximum vapor pressure of product at 130°F.
Wash. Admin. Code § 296-24-47507
Statutory Authority: RCW 49.17.010, [49.17].040 and[49.17].050 . 99-17-094, § 296-24-47507, filed 8/17/99, effective 12/1/99. Statutory Authority: Chapter 49.17 RCW. 94-15-096 (Order 94-07), § 296-24-47507, filed 7/20/94, effective 9/20/94; 88-23-054 (Order 88-25), § 296-24-47507, filed 11/14/88; Order 73-5, § 296-24-47507, filed 5/9/73 and Order 73-4, § 296-24-47507, filed 5/7/73.