9 Va. Admin. Code § 25-580-90

Current through Register Vol. 41, No. 9, December 16, 2024
Section 9VAC25-580-90 - Operation and maintenance of corrosion protection

All owners and operators of metal UST systems with corrosion protection must comply with the following requirements to ensure that releases due to corrosion are prevented until the UST system is permanently closed or undergoes a change-in-service pursuant to 9VAC25-580-320:

1. All corrosion protection systems must be operated and maintained to continuously provide corrosion protection to the metal components of that portion of the tank and piping that routinely contain regulated substances and are in contact with the ground.
2. All UST systems equipped with cathodic protection systems must be inspected for proper operation by a qualified cathodic protection tester in accordance with the following requirements:
a. Frequency. All cathodic protection systems must be tested within six months of installation and at least every three years thereafter; and
b. Inspection criteria. The criteria that are used to determine that cathodic protection is adequate as required by this section must be in accordance with a code of practice developed by a nationally recognized association.

NOTE: The following codes of practice may be used to comply with subdivision 2 of this section:

(1) NACE International Test Method TM0101, Measurement Techniques Related to Criteria for Cathodic Protection of Underground Storage Tank Systems;
(2) NACE International Test Method TM0497, Measurement Techniques Related to Criteria for Cathodic Protection on Underground or Submerged Metallic Piping Systems;
(3) Steel Tank Institute Recommended Practice R051, Cathodic Protection Testing Procedures for STI-P3® USTs;
(4) NACE International Standard Practice SP0285, External Control of Underground Storage Tank Systems by Cathodic Protection; or
(5) NACE International Standard Practice SP0169, Control of External Corrosion on Underground or Submerged Metallic Piping Systems.
3. UST systems with impressed current cathodic protection systems must also be inspected every 60 days to ensure the equipment is running properly. These systems only provide the necessary corrosion protection when in continuous operation. Such equipment shall be installed so that it cannot be inadvertently shut off.
4. For UST systems using cathodic protection, records of the operation of the cathodic protection must be maintained (in accordance with 9VAC25-580-120 ) to demonstrate compliance with the performance standards in this section. These records must provide the following:
a. The results of the last three inspections required in subdivision 3 of this section; and
b. The results of testing from the last two inspections required in subdivision 2 of this section.

9 Va. Admin. Code § 25-580-90

Derived from VR680-13-02 §3.2, eff. October 25, 1989; Amended, Virginia Register Volume 34, Issue 01, eff. 1/1/2018.

Statutory Authority: §§ 62-1.44.15 and 62.1-44.34:9 of the Code of Virginia; 42 USC § 6901 et seq.; 40 CFR "part"s 280 and 281.