Required Step 1 TOC reductions, indicated in Table 411.1, are based upon specified source water parameters. A waterworks practicing softening is required to meet the Step 1 TOC reductions in the far-right column (source water alkalinity greater than 120 mg/L) for the specified source water TOC.
TABLE 411.1Required Percentage Removals of TOCa,b | |||
SOURCE WATER TOC, mg/L | SOURCE WATER ALKALINITY, mg/L as CaCO3 | ||
0 - 60 | >60 - 120 | >120c | |
>2.0 - 4.0 | 35.0% | 25.0% | 15.0% |
>4.0 - 8.0 | 45.0% | 35.0% | 25.0% |
>8.0 | 50.0% | 40.0% | 30.0% |
aA waterworks meeting at least one of the conditions in subdivisions A 1 c (1) through A 1 c (6) of this section is not required to operate with enhanced coagulation. bA waterworks utilizing softening and meeting one of the alternative compliance criteria in subdivision A 1 d of this section is not required to operate with enhanced softening. cA waterworks practicing softening shall meet the TOC removal requirements in this column. |
TABLE 411.2Enhanced Coagulation | ||
ALKALINITY (mg/L as CaCO3) | TARGET pH | |
0 - 60 | 5.5 | |
>60 -120 | 6.3 | |
>120 - 240 | 7.0 | |
>240 | 7.5 |
[1-(treated water TOC/source water TOC)] X 100.
DISINFECTION BYPRODUCT | BEST AVAILABLE TECHNOLOGY | |
Bromate | Control of ozone treatment process to reduce production of bromate | |
Chlorite | Control of treatment processes to reduce disinfectant demand and control of disinfection treatment processes to reduce disinfectant levels |
DISINFECTION BYPRODUCT | BEST AVAILABLE TECHNOLOGY | |
TTHM and HAA5 | Enhanced coagulation or enhanced softening or GAC10, with chlorine as the primary and residual disinfectant |
DISINFECTION BYPRODUCT | BEST AVAILABLE TECHNOLOGY | |
TTHM and HAA5 | Enhanced coagulation or enhanced softening, plus GAC10; or NF with a molecular weight cutoff fewer than or equal to 1,000 Daltons; or GAC20 |
DISINFECTION BYPRODUCT | BEST AVAILABLE TECHNOLOGY | |
TTHM and HAA5 | A waterworks serving equal to or greater than 10,000 people: Improved distribution system and storage tank management to reduce residence time, plus the use of chloramines for residual disinfectant maintenance A waterworks serving fewer than 10,000 people: Improved distribution system and storage tank management to reduce residence time |