Current through Bulletin 2024-23, December 1, 2024
Section R432-500-28 - Lighting(1) Sodium and mercury vapor lights shall not be used inside the facility, but may be used as a source of exterior lighting.(2) The licensee shall ensure there is an accessible storeroom, stairway, ramp, exit, and entrance areas are illuminated by at least 20 foot-candles of light at floor level.(3) The licensee shall ensure that corridors are illuminated with a minimum of 20 foot-candles of light at floor level.(4) The licensee shall ensure other areas are provided with the following minimum foot-candles of light at working surfaces:(a) operating rooms, 50 foot-candles;(b) medication preparation areas, 50 foot-candles;(c) charting areas, 50 foot-candles;(d) reading areas, 50 foot-candles;(e) laundry areas, 30 foot-candles;(f) toilet, bath, and shower rooms, 30 foot-candles; and(g) nutritional area, 30 foot-candles.Utah Admin. Code R432-500-28
Amended by Utah State Bulletin Number 2023-17, effective 8/10/2023