Current through Bulletin 2024-23, December 1, 2024
Section R432-5-8 - Resident Support Areas(1) Occupational therapy service areas may be counted in the calculation of support space.(2) Physical Therapy, personal care room, and public waiting lobbies shall not be included in the calculation of support space.(3) There shall be resident living areas equipped with tables, reading lamps, and comfortable chairs designed to be usable by each resident.(4) There shall be a general purpose room with a minimum area of 100 square feet equipped with a table and comfortable chairs.(5) A minimum area of ten square feet per bed shall be provided for outdoor recreation. This space shall be provided in addition to the setbacks on street frontages required by local zoning ordinances.(6) An examination and treatment room shall be provided except when any resident rooms are single bed rooms. (a) An examination and treatment room may be shared by multiple nursing units.(b) When provided, the room shall have a minimum floor area of 100 square feet, excluding space for vestibules, toilet, closets, and work counters, whether fixed or moveable.(c) The room shall contain a lavatory equipped for handwashing, work counter, storage facilities, and a desk, counter, or shelf space for writing.(7) In addition to facility general storage areas, at least five square feet per bed shall be provided for resident storage.Utah Admin. Code R432-5-8
Amended by Utah State Bulletin Number 2022-06, effective 3/3/2022