Section R432-16-7 - Patient Rooms(1) The licensee shall ensure that:(a) a maximum room occupancy is two patients;(b) the minimum room areas for new construction, excluding toilets, closets, lockers, wardrobes, alcoves, or vestibules, measures 120 square feet in single-bedrooms and 100 square feet per bed in multiple-bed rooms;(c) existing buildings or spaces being licensed as a hospice shall have a minimum of 80 square feet of clear floor area per bed in multiple-bed areas and 100 square feet of clear floor area in single-bed rooms;(d) in multiple-bed rooms, clearance shall allow for the movement of beds and equipment without disturbing patients;(e) the dimensions and arrangement of rooms shall allow for a minimum of three feet clearance at one side, the foot, and between another bed;(f) there is a nurse call system and each bed is provided with a call device that functions as follows:(i) two call devices serving adjacent beds may be served by one calling station; and(ii) calls in a large inpatient hospice facility activate a visible signal in the corridor at the patient's door; and(g) a nurse emergency call device is provided at each inpatient toilet, bath, and shower room and is accessible to a collapsed patient lying on the floor. Inclusion of a pull cord may satisfy this standard(2) The licensee shall ensure the emergency call system is designed so that a signal activated at a patient's calling station will initiate a visible and audible signal distinct from the regular nurse call system and can be turned off only at the patient calling station. This signal shall activate:(a) an annunciator panel at the nurse station or other location appropriate to ensure immediate nurse notification; and(b) a visible signal in the corridor at the patient's door for emergency calls in a large hospice inpatient facility.(3) The licensee shall ensure each patient has access to a toilet room without having to enter the corridor area that includes:(a) one toilet room serves four or fewer beds and no more than two patient rooms;(b) the toilet room contains a toilet and sink; and(c) the toilet room door swings outward.(4) The licensee shall ensure at least one single-bed room with a private toilet room containing a toilet, sink, and bathing facility is provided for each eight beds.(5) In addition to the sink in the toilet room, in new construction or remodeling, the licensee shall ensure a sink is provided in the patient room.(6) The licensee shall ensure ventilation is represented in the department plans review as required in Rule R432-4.(7) The licensee shall ensure each resident room, intended for 24-hour occupancy, has an operable window open to the building exterior or to a courtyard that is open to the sky.(8) The licensee shall ensure that each patient closet is a minimum of 22 inches deep by 36 inches wide with a shelf to store clothing and a clothes rod positioned at 70 inches to hang full length garments.(9) The licensee shall ensure that visual privacy is provided for each patient in a multiple-bed room. Design for privacy shall not restrict patient access to the toilet, lavatory, or room entrance.Utah Admin. Code R432-16-7
Amended by Utah State Bulletin Number 2023-10, effective 5/5/2023