Utah Admin. Code 432-10-4

Current through Bulletin 2024-23, December 1, 2024
Section R432-10-4 - General Construction, Patient Facilities
(1) The requirements of R432-4-24 and the requirements of Sections 2.1 and 2.6 of the Guidelines for Design and Construction of Health Care Facilities 2010 edition (Guidelines) shall be met. Where a modification is cited, the modification supersedes conflicting requirements of the Guidelines.
(2) The maximum number of beds on each nursing unit shall be 60.
(a) The minimum number of beds in a nursing unit shall be four.
(b) Rooms and spaces comprising the nursing unit shall be contiguous.
(3) At least two single-bed rooms, with a private toilet room containing a toilet, lavatory, and bathing facility, shall be provided for each nursing unit.
(a) The minimum patient room area shall be 120 feet.
(b) In addition to the lavatory in the toilet room, in new construction a lavatory or handwashing sink shall be provided in the patient room.
(c) Ventilation shall be in accordance with Part 6, Table 7-1 of Guidelines with all air exhausted to the outside.
(4) The nurses' station shall have handwashing facilities located near the nurses' station and the drug distribution station. The nurses' toilet room, located in the unit, may also serve as a public toilet room.
(5) A nurse call system is not required in facilities that care for developmentally disabled or mentally retarded persons. With the prior approval of the Department, facilities which serve patients who pose a danger to themselves or others may modify the system to alleviate hazards to patients.
(6) Patient rooms shall include a wardrobe, closet, or locker having minimum clear dimensions of 22 inches deep by 36 inches wide, suitable for hanging full length garments.
(7) A clean workroom or clean holding room with a minimum area of 80 square feet for preparing patient care items which shall contain a counter, handwashing facilities, and storage facilities.
(a) The work counter and handwashing facilities may be omitted in rooms used only for storage and holding, as part of a larger system for distribution of clean and sterile supply materials.
(8) A soiled workroom with a minimum area of 80 square feet which shall contain a clinical sink, a sink equipped for handwashing, a work counter, waste receptacles and a linen receptacle.
(a) Handwashing sinks and work counters may be omitted in rooms used only for temporary holding of soiled, bagged materials.
(9) If a medication dispensing unit is used it shall be under visual control of staff, including double locked storage for controlled drugs.
(10) Clean Linen Storage.
(a) If a closed cart system is used it shall be stored in a room with a self closing door.
(b) Storage of a closed cart in an alcove in a corridor is prohibited.
(11) Each nursing unit shall have equipment to provide ice for patient treatment and nourishment.
(a) Ice making equipment may be located in the clean workroom or at the nourishment station if access is controlled by staff.
(b) Ice intended for human consumption shall be dispensed by self-dispensing ice makers.
(12) At least one room for toilet training, accessible from the nursing corridor, shall be provided on each floor containing a nursing unit.
(a) All fixtures in this room shall comply with the Americans with Disabilities Act and Architectural Barriers Act Accessibility Guidelines (ADA/ABA-AG).
(b) A toilet room, with direct access from the bathing area, shall be provided at each central bathing area.
(c) Doors to toilet rooms shall comply with ADA/ABA-AG. The doors shall permit access from the outside in case of an emergency.
(d) A handwashing fixture shall be provided for each toilet in each toilet room.
(13) Storage. There shall be an equipment storage room with a minimum area of 120 square feet for portable storage.
(14) Resident Support Areas Shall Include the Following:
(a) Occupational Therapy may be counted in the required space of Guidelines section 2.6-2.3 Patient Living Areas.
(b) Physical Therapy, personal care room and public waiting lobbies may not be included in the calculation of space of Guidelines section 2.6-2.3 Patient Living Areas.
(c) Storage space for recreation equipment and supplies shall be provided and secured for safety.
(d) There shall be a general purpose room with a minimum area of 100 square feet equipped with table, and comfortable chairs.
(e) A minimum area of ten square feet per bed shall be provided for outdoor recreation. Recreation areas shall be enclosed by a secure fence.
(15) An examination and treatment Room shall be provided except when all patient rooms are single-bed rooms.
(a) The examination and treatment room may be shared by multiple nursing units.
(b) The room shall have a minimum floor area of 100 square feet, excluding space for vestibules, toilet, closets, and work counters, whether fixed or movable.
(c) The minimum allowable room dimension shall be ten feet.
(d) The room shall contain a lavatory or sink equipped for handwashing; work counter; storage facilities; and desk, counter, or shelf space for writing.
(16) A room shall be arranged to permit evaluation of patient needs and progress.
(a) The room shall include a desk and work area for the evaluators, writing and work space for patients, and storage for supplies.
(b) If psychological services are provided, then the unit shall contain an office and work space for testing, evaluation, and counseling.
(c) If social services are provided, then the unit shall contain office space for private interviewing and counseling.
(d) If vocational services are provided, then the unit shall contain office and work space for vocational training, counseling, and placement.
(e) Evaluation, psychological services, social services, and vocational services may share the same office space when the owner provides evidence in the functional program that the needs of the population served are met in the proposed space arrangement.
(17) Pediatric and Adolescent Unit.
(a) Pediatric and adolescent nursing units shall comply with the spatial standards in section 2.2- 2.13 of the Guidelines.
(b) There shall be an area for hygiene, toileting, sleeping, and personal care for parents if the program allows parents to remain with young children.
(c) Service areas in the pediatric and adolescent nursing unit shall conform to the standards of section 2.2-2.13.6 of the Guidelines and the following:
(i) Multipurpose or individual rooms shall be provided in the nursing unit for dining, education, and recreation.
(ii) A minimum of 20 square feet per bed shall be provided.
(iii) Insulation, isolation and structural provisions shall minimize the transmission of impact noise through the floor, walls, or ceiling of multipurpose rooms.
(iv) Service rooms may be shared by more than one pediatric or adolescent nursing unit, but may not be shared with adult patient units.
(v) A patient toilet room, in addition to those serving bed areas, shall be conveniently located to each multipurpose room and to each central bathing facility.
(vi) Storage closets or cabinets for toys, educational, and recreational equipment shall be provided.
(d) At least one single-bed isolation room shall be provided in each pediatric unit. Each isolation room shall comply with the following:
(i) Room entry shall be through an adjacent work area which provides for aseptic control, including facilities separate from patient areas for handwashing, gowning, and storage of clean and soiled materials. The work area entry may be a separate, enclosed anteroom.
(ii) A separate, enclosed anteroom for an isolation room is not required but, when provided, shall include a viewing panel for staff observation of the patient from the anteroom.
(iii) One anteroom may serve several isolation rooms.
(iv) Toilet, bathing, and handwashing facilities shall be arranged to permit access from the bed area without entering or passing through the work area of the vestibule or anteroom.
(17) Rehabilitation therapy, Physical Therapy and Occupational Therapy areas shall include:
(a) Waiting areas to accommodate patients in wheelchairs, including room for turning wheelchairs.
(b) Storage space, with separate storage rooms for clean and soiled linen.

Utah Admin. Code R432-10-4