16 Tex. Admin. Code § 14.2304

Current through Reg. 49, No. 50; December 13, 2024
Section 14.2304 - General Facility Design
(a) LNG shall not be vented to the atmosphere under normal operations unless the vent leads to a safe point of discharge. Vent pipes or stacks shall have the open end suitably protected to prevent entrance of rain, snow, and other foreign material. Vent stacks shall have provision for drainage.
(b) Temperature monitoring systems shall be provided where the foundations supporting cryogenic containers and equipment could be adversely affected by freezing or frost heaving of the ground.

16 Tex. Admin. Code § 14.2304

The provisions of this §14.2304 adopted to be effective May 26, 2003, 28 TexReg 4100; Amended by Texas Register, Volume 46, Number 07, February 12, 2021, TexReg 1050, eff. 2/15/2021