Section 14.2119 - Transport Vehicle Loading and Unloading Facilities and Procedures

In addition to NFPA 59A §11.6, transport vehicle loading and unloading facilities shall meet the following requirements:

(1) Transfer piping, pumps, and compressors shall be installed with the following protective measures:
(A) protection from damage from vehicle movements in compliance with the guardrail and fencing requirements of § RSA 14.2101 of this title (relating to System Protection Requirements);
(B) isolation valves at both ends of containers with less than 2,000 gallon capacity, and a remote operating valve, automatic closure, or check valve to prevent backflow on containers of 2,000 gallons or more capacity;
(C) a check valve on piping for liquid transfer to minimize accidental release; and
(D) a line relief valve between every pair of isolation valves.
(2) Operating status indicators shall be provided in the transfer area.

16 Tex. Admin. Code § 14.2119