Current through December 10, 2024
Section 0720-26-.16 - DISASTER PREPAREDNESS(1) An ACLF shall have in effect and available for all supervisory personnel and staff written copies of the following disaster, refuge and/or evacuation plans readily available at all times:(a) Fire Safety Procedures Plan shall include:4. Evacuation procedures; and(b) Tornado/Severe Weather Procedures Plan shall include:2. Evacuation procedures.(c) Bomb Threat Procedures Plan shall include:2. Search team, searching the premises;3. Notification of authorities;4. Location of suspicious objects; and,5. Evacuation procedures.(d) Flood Procedure Plan, if applicable, shall include:2. Evacuation procedures; and3. Safety procedures following the flood.(e) Severe Cold Weather and Severe Hot Weather Procedure Plans shall include: 3. Evacuation procedures; and4. Emergency food service.(f) Earthquake Disaster Procedures Plan shall include:2. Evacuation procedures;3. Safety procedures; and(2) An ACLF shall comply with the following:(a) Maintain a detailed log with staff signatures designating training each employee receives regarding disaster preparedness.(b) Train all employees annually as required in the plans listed above and keep each employee informed with respect to the employee's duties under the plans.(c) Exercise each of the plans listed above annually.(3) An ACLF shall participate in the Tennessee Emergency Management Agency local/county emergency plan on an annual basis. Participation includes: (a) Filling out and submitting a questionnaire on a form to be provided by the Tennessee Emergency Management Agency; and(b) Maintaining documentation of participation that shall be made available to survey staff as proof of participation.(4) ACLFs which elect to have an emergency generator shall ensure that the generator is designed to meet the ACLF's HVAC and essential needs and shall have a minimum of twenty-four (24) hours of fuel designed to operate at its rated load. This requirement shall be coordinated with the Disaster Preparedness Plan or with the local resources. (a) All generators shall be exercised for thirty (30) minutes each month under full load, including automatic and manual transfer of equipment.(b) The emergency generator shall be operated at the existing connected load and not on dual power. The ACLF shall maintain a monthly log and have trained staff familiar with the generator's operation.Tenn. Comp. R. & Regs. 0720-26-.16
Public necessity rule filed May 13, 2009; effective through October 25, 2009. Emergency rule filed October 22, 2009; effective through April 20, 2010. Amendment filed September 24, 2009; effective December 23, 2009. Transferred from chapter 1200-08-25 pursuant to Public Chapter 1119 of 2022 effective 7/1/2022.Authority: T.C.A. §§ 68-11-202 and 68-11-209.