Fire extinguishers that are at least 2-A:10-B:C rated shall be installed for general building coverage at a rate of one for each 3,000 square feet and one additional 2-A:10-B:C rated extinguisher also located at the kitchen, laundry, and furnace room.
S.D. Admin. R. 44:78:03:04
General Authority: SDCL 34-12-13(3).
Law Implemented: SDCL 34-12-13(3).