S.D. Admin. R. 44:70:10:34

Current through Register Vol. 51, page 57, November 12, 2024
Section 44:70:10:34 - Receptacles or convenience outlets

Each resident bedroom shall have duplex receptacles as follows: one on each side of the head of each bed; receptacles for luminaries and motorized beds, if used; and one receptacle on another wall. Duplex receptacles for general use shall be installed approximately 50 feet apart in each corridor and within 25 feet of the end of the corridor.

S.D. Admin. R. 44:70:10:34

38 SDR 115, effective 1/9/2012.

General Authority: SDCL 34-12-13(4) and (14).

Law Implemented: SDCL 34-12-13(4) and (14).