Section 250-RICR-120-05-20.18 - Guidelines for Approvable Sampling and Analysis SchedulesA. Sampling 1. A source approved to burn alternative fuels may take a sample for analysis after each addition of alternative fuel to the fuel storage tank. Said sample should be taken from the fuel line between the feed pump and the burner at least six (6) hours after the addition but no later than eighteen (18) hours, or2. The source can sample the material prior to its addition to the storage tank.B. Analysis 1. Samples taken may be blended into a composite sample and analyzed for the following parameters according to the schedule listed below: Burning Rate (gallons/weeks) |
0-2,000 | 2-6,000 | 6-15,000 | 15,000+ |
Heating Value | Semiannually | Quarterly | Monthly | Biweekly |
Flash Point | Semiannually | Quarterly | Monthly | Biweekly |
Viscosity | Quarterly | Monthly | Biweekly | Weekly |
Halogen | Quarterly | Monthly | Biweekly | Weekly |
BS & Ws | Quarterly | Monthly | Biweekly | Weekly |
Lead | Quarterly | Monthly | Biweekly | Weekly |
PCB's | Quarterly | Monthly | Biweekly | Weekly |
Sulfur | Semiannually | Quarterly | Monthly | Biweekly |
Ash | Quarterly | Monthly | Biweekly | Weekly |
Arsenic | Quarterly | Monthly | Biweekly | Weekly |
Cadmium | Quarterly | Monthly | Biweekly | Weekly |
Chromium | Quarterly | Monthly | Biweekly | Weekly |
250 R.I. Code R. 250-RICR-120-05-20.18