Current through Register Vol. 54, No. 45, November 9, 2024
Section 51.21 - Minimum exits(a) There shall be a minimum of three exits reasonably remote from each other. No more than 50% of the required exit capacity shall exit into the same unseparated corridor network.(b) Basements used only for storage or mechanical equipment without any permanent occupancy shall have a minimum of two exit access paths except that the Department may permit a single exit access for basements of less than 1,000 square feet which are used only for storage or mechanical equipment without any permanent occupancy.