TABLE 1
Type of Tank | Protection | Minimum Distance in Feet From Property Line Which May be Built Upon, Including the Opposite Side of a Public Way | Minimum Distance in Feet From Nearest Side of Any Public Way or Nearest Building on Same Property (See Note) |
Floating roof | Protection for exposures | 1/2 times diameter of tank but need not exceed 90 feet | 1/6 times diameter of tank but need not exceed 30 feet |
None | Diameter of tank but need not exceed 175 feet | 1/6 times diameter of tank but need not exceed 30 feet | |
Vertical with weak roof to shell seam | Approved foam or inerting system on the tank | 1/2 times diameter of tank but need not exceed 90 feet and shall not be less than 5 feet | 1/6 times diameter of tank but need not exceed 30 feet and shall not be less than 5 feet |
Protection for exposures | Diameter of tank but need not exceed 175 feet | 1/3 times diameter of tank but need not exceed 60 feet | |
None | 2 times diameter of tank but need not exceed 350 feet | 1/3 times diameter of tank but need not exceed 60 feet | |
Horizontal and vertical with emergency relief venting to limit pressures to 21/2 psig | Approved inerting system on the tank or approved foam system on vertical tanks | 1/2 times Table 5 but shall not be less than 5 feet | 1/2 times Table 5 but shall not be less than 5 feet |
Protection for exposures | Table 5 | Table 5 | |
None | 2 times Table 5 | Table 5 |
NOTE-No pump or tank shall be placed within the legal right-of-way limits of any State highway or any highway under the jurisdiction of DOT.
TABLE 2
Type of Tank | Protection | Minimum Distance in Feet From Property Line Which May be Built Upon, Including the Opposite Side of aPublic Way | Minimum Distance in Feet From Nearest Side of Any Public Way or Nearest Building on Same Property (See Note) |
Any type | Protection for exposures | 1 1/2 times Table 5 but shall not be less than 25 feet | 1 1/2 times Table 5 but shall not be less than 25 feet |
None | 3 times Table 5 but shall not be less than 50 feet | 1 1/2 times Table 5 but shall not be less than 25 feet |
Note-No pump or tank shall be placed within the legal right-of-way limits of any State highway or any highway under the jurisdiction of DOT.
TABLE 3
Type of Tank | Protection | Minimum Distance in Feet From Property Line Which May be Built Upon, Including the Opposite Side of a Public Way | Minimum Distance in Feet From Nearest Side of Any Public Way or Nearest Building on Same Property (See Note) |
Floating roof | Protection for exposures | Diameter of tank but need not exceed 175 feet | 1/3 times diameter of tank but need not exceed 60 feet |
None | 2 times diameter of tank but need not exceed 350 feet | 1/3 times diameter of tank but need not exceed 60 feet | |
Approved foam or inerting system | Diameter of tank but need not exceed 175 feet | 1/3 times diameter of tank but need not exceed 60 feet | |
Fixed roof | Protection for exposures | 2 times diameter of tank but need not exceed 350 feet | 2/3 times diameter of tank but need not exceed 120 feet |
None | 4 times diameter of tank but need not exceed 350 feet | 2/3 times diameter of tank but need not exceed 120 feet |
Note-No pump or tank shall be placed within the legal right-of-way limits of any State highway or any highway under the jurisdiction of DOT.
TABLE 4
Type of Tank | Protection | Minimum Distance in Feet From Property Line Which May be Built Upon, Including the Opposite Side of a Public Way | Minimum Distance in Feet From Nearest Side of Any Public Way or Nearest Building on Same Property (See Note) |
Horizontal and vertical tanks with emergency relief venting to permit pressure not in excess of 21/2 psig | Tank protected with any one of the following: approved water spray, approved inerting, approved insulation and refrigeration, approved barricade | Table 5 but not less than 25 feet | Not less than 25 feet |
Protection for exposures | 2 1/2 times Table 5 but not less than 50 feet | Not less than 50 feet | |
None | 5 times Table 5 but not less than 100 feet | Not less than 100 feet | |
Horizontal and vertical tanks with emergency relief venting to permit pressure over 21/2 psig | Tank protected with any one of the following: approved water spray, approved inerting, approved insulation and refrigeration, approved barricade | 2 times Table 5 but not less than 50 feet | Not less than 50 feet |
Protection for exposures | 4 times Table 5 but not less than 100 feet | Not less than 100 feet | |
None | 8 times Table 5 but not less than 150 feet | Not less than 150 feet |
Note-No pump or tank shall be placed within the legal right-of-way limits of any State highway or any highway under the jurisdiction of DOT.
TABLE 5
Capacity of Tank (in gallons) | Minimum Distance in Feet From Property Line Which May be Built Upon, Including the Opposite Side of a Public Way | Minimum Distance in Feet From Nearest Side of Any Public Way or Nearest Building on Same Property See Note) |
275 or less | 5 | 5 |
276 to 750 | 10 | 5 |
751 to 12,000 | 15 | 5 |
12,001 to 30,000 | 20 | 5 |
30,001 to 50,000 | 30 | 10 |
50,001 to 100,000 | 50 | 15 |
100,001 to 500,000 | 80 | 25 |
500,001 to 1,000,000 | 100 | 35 |
1,000,001 to 2,000,000 | 135 | 45 |
2,000,001 to 3,000,000 | 165 | 55 |
3,000,001 or more | 175 | 60 |
NOTE-No pump or tank shall be placed within the legal right-of-way limits of any State highway or any highway under the jurisdiction of DOT.
34 Pa. Code § 14a.1
This section cited in 34 Pa. Code § 14a.33 (relating to Class II and Class III liquids); 34 Pa. Code § 14a.46 (relating to storage outside of buildings); 34 Pa. Code § 14a.105 (relating to loading and unloading); 34 Pa. Code § 14a.111 (relating to storage and handling); 34 Pa. Code § 14a.141 (relating to scope and application); 34 Pa. Code § 14a.151 (relating to scope and application); and 34 Pa. Code § 14a.161 (relating to general provisions).