Section 918-225-0370 - Coil-Type Water BoilersCoil-type water boilers, where the water can flash into steam when released directly to the atmosphere through a manually operated nozzle, are exempt from ORS 480.510 to 480.665 if the following conditions are met:
(1) There is no drum, header, or other steam space;(2) No steam is generated within the coil;(3) Tubing outside diameter does not exceed one inch;(4) Pipe size does not exceed NPS 3/4;(5) Nominal water capacity does not exceed six gallons;(6) Water temperature does not exceed 350° F.;(7) Adequate safety relief valves and controls are provided.Or. Admin. Code § 918-225-0370