Current through Vol. 42, No. 7, December 16, 2024
Section 252:631-3-17 - Water system connections(a) PWS systems must not allow the connection of a new customer without an approved sewage disposal system, as defined in OAC 252:641 (Individual and Small Public On-Site Sewage Disposal Systems) or OAC 252:656 (Water Pollution Control Construction).(b) PWS systems shall: (1) not allow a physical connection between a line carrying a public drinking water supply and a line carrying water of unknown or questionable quality.(2) not allow connections from any PWS system to any device or system that poses a health threat unless it is equipped with an air gap of at least 6 inches or two pipe diameters, whichever is larger, above the overflow or drain pipe. The installation of a reduced pressure zone backflow prevention device will be considered in lieu of an air gap. To allow maintenance on the backflow prevention device, the design shall include a diversion line with equal backflow prevention. Do not locate backflow prevention devices in a pit or vault where they can become submerged. A fire suppression system is not considered a hazardous water supply.(3) not allow a cross-connection between a public water system and any private water system.(4) provide an air gap at all points where finished water is connected to a drain.Okla. Admin. Code § 252:631-3-17
Added at 17 Ok Reg 1987, eff 6-12-00; Amended at 20 Ok Reg 1153, eff 6-1-03; Amended at 25 Ok Reg 2305, eff 7-11-08