Current through Vol. 42, No. 8, January 2, 2025
Section 165:35-15-17 - Schedule for testing demand metersThe following schedule is required for testing demand meters:
(1) Block interval demand-registers-equipped watt-hour meters. (A) Meters with surge-proof magnets - 12 years.(B) Meters without surge-proof magnets - 8 years.(2) Block interval graphic watt-hour demand meters - 2 years.(3) Lagged demand meters - 8 years.(4) Pulse recorders and pulse-operated demand meters in combination with pulse-initiator-equipped watt-hour meters - 2 years. If a comparison is made between the meter registration and the recorder registration each billing period, and the recorder registration agrees within one percent (1%) of that registered by the associated meter, the schedule for pulse recorders and pulse-operated demand meters should be as indicated in (A) and (B) of this paragraph. If recorder meter registration checks do not agree within one percent (1%), the demand metering equipment should be tested. (A) Meters with surge-proof magnets - 16 years.(B) Meters without surge-proof magnets - 8 years.Okla. Admin. Code § 165:35-15-17
Amended at 10 Ok Reg , eff 6-25-93