In order for the application to be reviewed by the EDU under the level 2 review procedure, the applicant's DER must meet the following requirements:
Line Voltage | Nominal Nameplate Capacity | Nominal Nameplate Capacity if located on a 600 amp line and within 2.5 feeder miles of substation |
less than or equal to 5kV | less than or equal to 500 kW | less than 2 MW |
5kV less than or equal to 15 kV | less than or equal to 2MW | less than 3 MW |
15 kV less than or equal to 30 kV | less than or equal to 3MW | less than 4 MW |
30 kV less than or equal to 69 kV | less than or equal to 4MW | less than 5 MW |
Primary Distribution Line Configuration | Interconnection to Primary Distribution Line |
Three phase, three wire | If a three-phase or single-phase DER, interconnection must be phase-to-phase |
Three phase, four wire | If a three-phase (effectively grounded) or single phase DER, interconnection must be line-to-neutral |
The EDU's tariff for level 2 review processing fees will include the following:
Ohio Admin. Code 4901:1-22-07
Five Year Review (FYR) Dates: 5/3/2027
Promulgated Under: 111.15
Statutory Authority: 4928.06
Rule Amplifies: 4928.11
Prior Effective Dates: 09/18/2000, 10/22/2007, 07/10/2014, 06/01/2022