Exceptions:
Exception: Storage of ammonium nitrate in magazines with blasting agents shall comply with the requirements of NFPA 495 as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Storage of smokeless propellant, black powder and small arms primers for personal use and not for resale in accordance with paragraph (F)(5606) of this rule.
Exception:Permit limitations on the quantity of fireworks possessed or stored at a licensed premises for fireworks, as that term is defined in section 3743.01(BB) of the Revised Code, shall be approved by the state fire marshal before any enforcement of such provisions by a local fire code official.
Exception: Gelatin dynamite.
Table 5601.8.1(1)
Application of separation distance (Q-D) tables-Division 1.1, 1.2 and 1.5 explosivesa,b,c
Item | Magazine | Q-D | Operating building | Q-D | Inhabited building | Q-D | Public traffic route | Q-D |
Magazine | Table 5604.5.2(1) of this rule | IMD | Table 5605.3of this rule | ILD or IPD | Table 5604.5.2(1) of this rule | IBD | Table 5604.5.2(1) of this rule | PTR |
Operating building | Table 5604.5.2(1) of this rule | ILD or IPD | Table 5605.3of this rule | ILD or IPD | Table 5604.5.2(1) of this rule | IBD | Table 5604.5.2(1) of this rule | PTR |
Inhabited building | Table 5604.5.2(1) of this rule | IBD | Table 5604.5.2(1) of this rule | IBD | Not applicable | Not applicable | Not applicable | Not applicable |
Public traffic route | Table 5604.5.2(1) of this rule | PTR | Table 5604.5.2(1) of this rule | PTR | Not applicable | Not applicable | Not applicable | Not applicable |
For SI: 1 foot = 304.8 mm.
a. The minimum separation distance (D0) shall be 60 feet. Where a building or magazine containing explosives is barricaded, the minimum distance shall be 30 feet.
b. Linear interpolation between tabular values in the referenced Q-D tables shall not be allowed. Nonlinear interpolation of the values shall be allowed subject to an approved technical opinion and report prepared in accordance with paragraph (D)(7)(b)(104.7.2) of rule 1301:7-7-01 of the Administrative Code.
c. For definitions of Quantity-Distance abbreviations IBD, ILD, IMD, IPD and PTR, see rule 1301:7-7-02 of the Administrative Code.
Table 5601.8.1(2)
Application of separation distance (Q-D) tables-Division 1.3 explosivesa,b,c
Item | Magazine | Q-D | Operating building | Q-D | Inhabited building | Q-D | Public traffic route | Q-D |
Magazine | Table 5604.5.2(2) of this rule | IMD | Table 5604.5.2(2) of this rule | ILD or IPD | Table 5604.5.2(2) of this rule | IBD | Table 5604.5.2(2) of this rule | PTR |
Operating building | Table 5604.5.2(2) of this rule | ILD or IPD | Table 5604.5.2(2) of this rule | ILD or IPD | Table 5604.5.2(2) of this rule | IBD | Table 5604.5.2(2) of this rule | PTR |
Inhabited building | Table 5604.5.2(2) of this rule | IBD | Table 5604.5.2(2) of this rule | IBD | Not applicable | Not applicable | Not applicable | Not applicable |
Public traffic route | Table 5604.5.2(2) of this rule | PTR | Table 5604.5.2(2) of this rule | PTR | Not applicable | Not applicable | Not applicable | Not applicable |
For SI: 1 foot = 304.8 mm.
a. The minimum separation distance (D0) shall be not less than 50 feet.
b. Linear interpolation between tabular values in the referenced Q-D table shall be allowed.
c. For definitions of Quantity-Distance abbreviations IBD, ILD, IMD, IPD and PTR, see rule 1301:7-7-02 of the Administrative Code.
Table 5601.8.1(3)
Application of separation distance (Q-D) tables-Division 1.4 explosivesa,b,c,d
Item | Magazine | Q-D | Operating building | Q-D | Inhabited building | Q-D | Public traffic route | Q-D |
Magazine | Table 5604.5.2(3) of this rule | IMD | Table 5604.5.2(3) of this rule | ILD or IPD | Table 5604.5.2(3) of this rule | IBD | Table 5604.5.2(3) of this rule | PTR |
Operating building | Table 5604.5.2(3) of this rule | ILD or IPD | Table 5604.5.2(3) of this rule | ILD or IPD | Table 5604.5.2(3) of this rule | IBD | Table 5604.5.2(3) of this rule | PTR |
Inhabited building | Table 5604.5.2(3) of this rule | IBD | Table 5604.5.2(3) of this rule | IBD | Not applicable | Not applicable | Not applicable | Not applicable |
Public traffic route | Table 5604.5.2(3) of this rule | PTR | Table 5604.5.2(3) of this rule | PTR | Not applicable | Not applicable | Not applicable | Not applicable |
For SI: 1 foot = 304.8 mm.
a. The minimum separation distance (D0) shall be not less than 50 feet.
b. Linear interpolation between tabular values in the referenced (Q-D) table shall not be allowed.
c. For definitions of Quantity-Distance abbreviations IBD, ILD, IMD, IPD and PTR, see rule 1301:7-7-02 of the Administrative Code.
d. This table shall not apply to consumer fireworks, 1.4 G.
Exception: Where the TNT equivalence of the explosive material has been determined, the equivalence is allowed to be used to establish the net explosive weight.
"Ammonium nitrate."
"Authority having jurisdiction."
"Barricade."
"Artificial barricade."
"Natural barricade."
"Barricaded."
"Beer and intoxicating liquor."
"Black match."
"Blast area."
"Blast site."
"Blaster."
"Blasting agent."
"Booby trap."
"Break."
"Bullet resistant."
"Cigarette load."
"Controlled substance."
"CPSC."
"Detonating cord."
"Detonation."
"Detonator."
"Discharge site."
"Display site."
"DOTn."
"Explosive."
"High explosive."
"Low explosive."
"Mass-detonating explosives."
"UN/DOTn Class 1 explosives."
"Division 1.1."
"Division 1.2."
"Division 1.3."
"Division 1.4."
"Division 1.5."
"Division 1.6."
"Explosive material."
"Fallout area."
"Fireworks."
"1.1 G Fireworks."
"1.2 G Fireworks."
"1.3 G Fireworks."
"1.4 G Fireworks."
"1.4 G Special effects fireworks."
"1.4 S Fireworks."
"1.4 S Special effects fireworks."
"Fireworks exhibition."
"Fireworks incident."
"Fireworks incident site."
"Fireworks plant."
"Flame effect."
"Highway."
"Inhabited building."
"Interlinked fire detection."
"Licensed building."
"Licensed exhibitor of fireworks or licensed exhibitor."
"Licensed exhibitor of indoor fireworks."
"Licensed exhibitor of outdoor/indoor fireworks."
"Licensed manufacturer of fireworks or licensed manufacturer."
"Licensed premises."
"Licensed wholesaler of fireworks or licensed wholesaler."
"List of licensed exhibitors."
"List of licensed manufacturers."
"List of licensed wholesalers."
"Magazine."
"Indoor."
"Type 1."
"Type 2."
"Type 3."
"Type 4."
"Type 5."
"Manufacturing of fireworks."
"Mortar."
"Navigable waters."
"Net explosive weight (net weight)."
"Novelties and trick noisemakers."
"Operating building."
"Operating line."
"Party popper."
"Plosophoric material."
"Processing of fireworks."
"Proximate audience."
"Public Traffic Route (PTR)."
"Pyrotechnic article."
"Pyrotechnic composition."
"Pyrotechnic special effect."
"Pyrotechnic special-effect material."
"Pyrotechnics."
"Quantity-Distance (Q-D)."
"Inhabited Building Distance (IBD)."
"Intermagazine Distance (IMD)."
"Intraline Distance (ILD) or Intraplant Distance (IPD)."
"Minimum separation distance (D0)."
"Railroad."
"Railway."
"Ready box."
"Representative sample showroom."
"Retail sale or sell at retail."
"Small arms ammunition."
"Small arms primers."
"Smoke device."
"Smokeless propellants."
"Snake or glow worm."
"Snapper."
"Special industrial explosive device."
"Storage location."
"Theft resistant."
"Trick match."
"Wholesale sale or sell at wholesale."
"Wire sparkler."
"Particular location."A licensed premises and, regardless of when approved, any storage location approved in accordance with section 3743.04 or 3743.17 of the Revised Code and this rule.
"Person."Any person or entity, in whatever form or name, that acquires possession of a manufacturer or wholesaler of fireworks license issued pursuant to this rule by transfer of possession of license, whether that transfer occurs by purchase, assignment, inheritance, bequest, stock transfer, or any other type of transfer, on the condition that the transfer is in accordance with division (D) of section 3743.04 of the Revised Code or division (D) of section 3743.17 of the Revised Code and is approved by the state fire marshal.
Exception: Where only Division 1.4 G (consumer fireworks) are handled, records need only be maintained for a period of 3 years.
Exception: Loss of Division 1.4 G (consumer fireworks) need not be reported to the Bureau of Alcohol, Tobacco, Firearms and Explosives.
Exceptions:
Table 5604.3
Storage amounts and magazine requirements for explosives, explosive materials and fireworks, 1.3 G maximum allowable quantity per control area
New UN/DOTn division | Old DOTn class | ATF/OSHA class | Indoora (pounds) | Outdoor (pounds) | Magazine type required | |||||||
Unprotected | Cabinet | Sprinklers | Sprinklers & cabinet | 1 | 2 | 3 | 4 | 5 | ||||
1.1b | A | High | 0 | 0 | 1 | 2 | 1 | X | X | X | - | - |
1.2 | A | High | 0 | 0 | 1 | 2 | 1 | X | X | X | - | - |
1.2 | B | Low | 0 | 0 | 1 | 1 | 1 | X | X | X | X | - |
1.3 | B | Low | 0 | 0 | 5 | 10 | 1 | X | X | X | X | - |
1.4c | B | Low | 0 | 0 | 50 | 100 | 1 | X | X | X | X | - |
1.5 | C | Low | 0 | 0 | 1 | 2 | 1 | X | X | X | X | - |
1.5 | Blasting agent | Blasting agent | 0 | 0 | 1 | 2 | 1 | X | X | X | X | X |
1.6 | Not applicable | Not applicable | 0 | 0 | 1 | 2 | 1 | X | X | X | X | X |
For SI: 1 pound = 0.454 kg, 1 pound per gallon = 0.12 kg per liter, 1 ounce = 28.35 g.
a. A factor of 10 pounds per gallon shall be used for converting pounds (solid) to gallons (liquid) in accordance with paragraph (C)(1)(b)(5003.1.2) of rule 1301:7-7-50 of the Administrative Code.
b. Black powder shall be stored in a Type 1, 2, 3 or 4 magazine as provided for in paragraph (D)(3)(a)(5604.3.1) of this rule.
c. This table shall not apply to consumer fireworks, 1.4 G.
Exceptions:
Exception: Day boxes used for the storage of in-process material in accordance with paragraph (E)(6)(d)(i)(5605.6.4.1) of this rule.
Table 5604.5.2(1)
American table of distances for storage of explosives as approved by the Institute of makers of explosives and revised June 1991a
Quantity of explosive materialsc | Distances in feet | ||||||||
Inhabited buildings | Public highways with traffic volume less than 3,000 vehicles per day | Public highways with traffic volume greater than 3,000 vehicles per day and passenger railways | Separation of magazinesd | ||||||
Pounds over | Pounds not over | Barricaded | Unbarricaded | Barricaded | Unbarricaded | Barricaded | Unbarricaded | Barricaded | Unbarricaded |
0 5 10 20 30 | 5 10 20 30 40 | 70 90 110 125 140 | 140 180 220 250 280 | 30 35 45 50 55 | 60 70 90 100 110 | 51 64 81 93 103 | 102 128 162 186 208 | 6 8 10 11 12 | 12 16 20 22 24 |
40 50 75 100 125 | 50 75 100 125 150 | 150 170 190 200 215 | 300 340 380 400 430 | 60 70 75 80 85 | 120 140 150 160 170 | 110 127 139 150 159 | 220 254 278 300 318 | 14 15 16 18 19 | 28 30 32 36 38 |
150 200 250 300 400 | 200 250 300 400 500 | 235 255 270 295 320 | 470 510 540 590 640 | 95 105 110 120 130 | 190 210 220 240 260 | 175 189 201 221 238 | 350 378 402 442 476 | 21 23 24 27 29 | 42 46 48 54 58 |
500 600 700 800 900 | 600 700 800 900 1,000 | 340 355 375 390 400 | 480 710 750 780 800 | 135 145 150 155 160 | 270 290 300 310 320 | 253 266 278 289 300 | 506 532 556 578 600 | 31 32 33 35 36 | 62 64 66 70 72 |
1,000 1,200 1,400 1,600 1,800 | 1,200 1,400 1,600 1,800 2,000 | 425 450 470 490 505 | 850 900 940 980 1,010 | 165 170 175 180 185 | 330 340 350 360 370 | 318 336 351 366 378 | 636 672 702 732 756 | 39 41 43 44 45 | 78 82 86 88 90 |
2,000 2,500 3,000 4,000 5,000 | 2,500 3,000 4,000 5,000 6,000 | 545 580 635 685 730 | 1,090 1,160 1,270 1,370 1,460 | 190 195 210 225 235 | 380 390 420 450 470 | 408 432 474 513 546 | 816 864 948 1,026 1,092 | 49 52 58 61 65 | 98 104 116 122 130 |
6,000 7,000 8,000 9,000 10,000 | 7,000 8,000 9,000 10,000 12,000 | 770 800 835 865 875 | 1,540 1,600 1,670 1,730 1,750 | 245 250 255 260 270 | 490 500 510 520 540 | 573 600 624 645 687 | 1,146 1,200 1,248 1,290 1,374 | 68 72 75 78 82 | 136 144 150 156 164 |
12,000 14,000 16,000 18,000 20,000 | 14,000 16,000 18,000 20,000 25,000 | 885 900 940 975 1,055 | 1,770 1,800 1,880 1,950 2,000 | 275 280 285 290 315 | 550 560 570 580 630 | 723 756 786 813 876 | 1,446 1,512 1,572 1,626 1,752 | 87 90 94 98 105 | 174 180 188 196 210 |
25,000 30,000 35,000 40,000 45,000 | 30,000 35,000 40,000 45,000 50,000 | 1,130 1,205 1,275 1,340 1,400 | 2,000 2,000 2,000 2,000 2,000 | 340 360 380 400 420 | 680 720 760 800 840 | 933 981 1,026 1,068 1,104 | 1,866 1,962 2,000 2,000 2,000 | 112 119 124 129 135 | 224 238 248 258 270 |
50,000 55,000 60,000 65,000 70,000 | 55,000 60,000 65,000 70,000 75,000 | 1,460 1,515 1,565 1,610 1,655 | 2,000 2,000 2,000 2,000 2,000 | 440 455 470 485 500 | 880 910 940 970 1,000 | 1,140 1,173 1,206 1,236 1,263 | 2,000 2,000 2,000 2,000 2,000 | 140 145 150 155 160 | 280 290 300 310 320 |
75,000 80,000 85,000 90,000 95,000 | 80,000 85,000 90,000 95,000 100,000 | 1,695 1,730 1,760 1,790 1,815 | 2,000 2,000 2,000 2,000 2,000 | 510 520 530 540 545 | 1,020 1,040 1,060 1,080 1,090 | 1,293 1,317 1,344 1,368 1,392 | 2,000 2,000 2,000 2,000 2,000 | 165 170 175 180 185 | 330 340 350 360 370 |
100,000 110,000 120,000 130,000 140,000 | 110,000 120,000 130,000 140,000 150,000 | 1,835 1,855 1,875 1,890 1,900 | 2,000 2,000 2,000 2,000 2,000 | 550 555 560 565 570 | 1,100 1.110 1,120 1,130 1,140 | 1,437 1,479 1,521 1,557 1,593 | 2,000 2,000 2,000 2,000 2,000 | 195 205 215 225 235 | 390 410 430 450 470 |
150,000 160,000 170,000 180,000 190,000 | 160,000 170,000 180,000 190,000 200,000 | 1,935 1,965 1,990 2,010 2,030 | 2,000 2,000 2,000 2,010 2,030 | 580 590 600 605 610 | 1,160 1,180 1,200 1,210 1,220 | 1,629 1,662 1,695 1,725 1,755 | 2,000 2,000 2,000 2,000 2,000 | 245 255 265 275 285 | 490 510 530 550 570 |
200,000 210,000 230,000 250,000 275,000 | 210,000 230,000 250,000 275,000 300,000b | 2,055 2,100 2,155 2,215 2,275 | 2,055 2,100 2,155 2,215 2,275 | 620 635 650 670 690 | 1,240 1,270 1,300 1,340 1,380 | 1,782 1,836 1,890 1,950 2,000 | 2,000 2,000 2,000 2,000 2,000 | 295 315 335 360 385 | 590 630 670 720 770 |
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
a. This table applies only to the manufacture and permanent storage of commercial explosive materials. It is not applicable to transportation of explosives or any handling or temporary storage necessary or incident thereto. It is not intended to apply to bombs, projectiles or other heavily encased explosives.
b. Storage in excess of 300,000 pounds of explosive materials in one magazine is not allowed.
c. Where a manufacturing building on an explosive materials plant site is designed to contain explosive materials, such building shall be located with respect to its proximity to inhabited buildings, public highways and passenger railways based on the maximum quantity of explosive materials permitted to be in the building at one time.
d. Where two or more storage magazines are located on the same property, each magazine shall comply with the minimum distances specified from inhabited buildings, railways and highways, and, in addition, they should be separated from each other by not less than the distances shown for separation of magazines, except that the quantity of explosives in detonator magazines shall govern in regard to the spacing of said detonator magazines from magazines containing other explosive materials. Where any two or more magazines are separated from each other by less than the specified separation of magazine distances, then two or more such magazines, as a group, shall be considered as one magazine, and the total quantity of explosive materials stored in such group shall be treated as if stored in a single magazine located on the site of any magazine in the group and shall comply with the minimum distances specified from other magazines, inhabited buildings, railways and highways.
Table 5604.5.2(2)
Table of distances (Q-D) for buildings and magazines containing explosives-Division 1.3 mass-fire hazarda,b,c
Quantity of Division 1.3 explosives (net explosives weight) | Distances in feet | ||||
Pounds over | Pounds not over | Inhabited building distance (IBD) | Distance to public traffic route (PTR) | Intermagazine distance (IMD) | Intraline distance (ILD) or Intraplant distance (IPD) |
0 | 1,000 | 75 | 75 | 50 | 50 |
1,000 | 5,000 | 115 | 115 | 75 | 75 |
5,000 | 10,000 | 150 | 150 | 100 | 100 |
10,000 | 20,000 | 190 | 190 | 125 | 125 |
20,000 | 30,000 | 215 | 215 | 145 | 145 |
30,000 | 40,000 | 235 | 235 | 155 | 155 |
40,000 | 50,000 | 250 | 250 | 165 | 165 |
50,000 | 60,000 | 260 | 260 | 175 | 175 |
60,000 | 70,000 | 270 | 270 | 185 | 185 |
70,000 | 80,000 | 280 | 280 | 190 | 190 |
80,000 | 90,000 | 295 | 295 | 195 | 195 |
90,000 | 100,000 | 300 | 300 | 200 | 200 |
100,000 | 200,000 | 375 | 375 | 250 | 250 |
200,000 | 300,000 | 450 | 450 | 300 | 300 |
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
a. Black powder, where stored in magazines, is defined as low explosive by the Bureau of Alcohol, Tobacco, Firearms and Explosives (BATF).
b. For quantities less than 1,000 pounds, the required distances are those specified for 1,000 pounds. The use of lesser distances is allowed where supported by approved test data and/or analysis.
c. Linear interpolation of explosive quantities between table entries is allowed.
Table 5604.5.2(3)
Table of distances (Q-D) for buildings and magazines containing explosives-Division 1.4c
Quantity of Division 1.4 explosives (net explosives weight) | Distances in feet | ||||
Pounds over | Pounds not over | Inhabited building distance (IBD) | Distance to public traffic route (PTR) | Intermagazine distancea,b (IMD) | Intraline distance (ILD) or Intraplant distancea (IPD) |
50 | Not limited | 100 | 100 | 50 | 50 |
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
a. A separation distance of 100 feet is required for buildings other than Type I or Type II construction as defined in the building code listed in rule 1301:7-7-80 of the Administrative Code.
b. For earth-covered magazines, specific separation is not required.
1. Earth cover material used for magazines shall be relatively cohesive. Solid or wet clay and similar types of soil are too cohesive and shall not be used. Soil shall be free from unsanitary organic matter, trash, debris and stones heavier than 10 pounds or larger than 6 inches in diameter. Compaction and surface preparation shall be provided, as necessary, to maintain structural integrity and avoid erosion. Where cohesive material cannot be used, as in sandy soil, the earth cover over magazines shall be finished with a suitable material to ensure structural integrity.
2. The earth fill or earth cover between earth-covered magazines shall be either solid or sloped, in accordance with the requirements of other construction features, but not less than 2 feet of earth cover shall be maintained over the top of each magazine. To reduce erosion and facilitate maintenance operations, the cover shall have a slope of 2 horizontal to 1 vertical.
c. Restricted to articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives regulations, or unpacked articles used in process operations that do not propagate a detonation or deflagration between articles. This table shall not apply to consumer fireworks, 1.4 G.
"DANGER!
NEVER FIGHT EXPLOSIVE FIRES.
EXPLOSIVES ARE STORED ON THIS SITE
CALL ___________"
The sign shall be weather-resistant with a reflective surface and have lettering not less than 2 inches (51 mm) high.
Exceptions:
Exception: Fireworks manufacturing buildings separated in accordance with NFPA 1124 as listed in rule 1301:77-80 of the Administrative Code.
The quantity of explosives in an operating building shall be the net weight of all the explosives contained therein. Distances shall be based on the hazard division requiring the greatest separation, unless the aggregate explosive weight is divided by approved walls or shields designed for that purpose. Where dividing a quantity of explosives into smaller stacks, a suitable barrier or adequate separation distance shall be provided to prevent propagation from one stack to another.
Where distance is used as the sole means of separation within a building, such distance shall be established by testing. Testing shall demonstrate that propagation between stacks will not result. Barriers provided to protect against explosive effects shall be designed and installed in accordance with approved standards.
Table 5605.3
Minimum intraline (intraplant) separation distances (ILD or IPD) between barricaded operating buildings containing explosives-Division 1.1, 1.2 or 1.5 -mass-explosion hazarda
Net explosive weight | Net explosive weight | ||||
Pounds over | Pounds not over | Intraline distance (ILD) or intraplant distance (IPD) (feet) | Pounds over | Pounds not over | Intraline distance (ILD) or intraplant distance (IPD) (feet) |
0 | 50 | 30 | 20,000 | 25,000 | 265 |
50 | 100 | 40 | 25,000 | 30,000 | 280 |
100 | 200 | 50 | 30,000 | 35,000 | 295 |
200 | 300 | 60 | 35,000 | 40,000 | 310 |
300 | 400 | 65 | 40,000 | 45,000 | 320 |
400 | 500 | 70 | 45,000 | 50,000 | 330 |
500 | 600 | 75 | 50,000 | 55,000 | 340 |
600 | 700 | 80 | 55,000 | 60,000 | 350 |
700 | 800 | 85 | 60,000 | 65,000 | 360 |
800 | 900 | 90 | 65,000 | 70,000 | 370 |
900 | 1,000 | 95 | 70,000 | 75,000 | 385 |
1,000 | 1,500 | 105 | 75,000 | 80,000 | 390 |
1,500 | 2,000 | 115 | 80,000 | 85,000 | 395 |
2,000 | 3,000 | 130 | 85,000 | 90,000 | 400 |
3,000 | 4,000 | 140 | 90,000 | 95,000 | 410 |
4,000 | 5,000 | 150 | 95,000 | 100,000 | 415 |
5,000 | 6,000 | 160 | 100,000 | 125,000 | 450 |
6,000 | 7,000 | 170 | 125,000 | 150,000 | 475 |
7,000 | 8,000 | 180 | 150,000 | 175,000 | 500 |
8,000 | 9,000 | 190 | 175,000 | 200,000 | 525 |
9,000 | 10,000 | 200 | 200,000 | 225,000 | 550 |
10,000 | 15,000 | 225 | 225,000 | 250,000 | 575 |
15,000 | 20,000 | 245 | 250,000 | 275,000 | 600 |
------- | ------- | ------- | 275,000 | 300,000 | 635 |
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg.
a. Where a building or magazine containing explosives is not barricaded, the intraline distances shown in this table shall be doubled.
Exception: Fireworks manufacturing buildings constructed and operated in accordance with NFPA 1124 as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Fireworks manufacturing buildings constructed and operated in accordance with NFPA 1124 as listed in rule 1301:7-7-80 of the Administrative Code.
Exception: Composition that has been loaded or pressed into tubes or other containers as consumer fireworks.
Exception: Approved drying or curing operations.
Exception: Approved repackaging of damaged containers of smokeless propellant into containers of the same type and size as the original container.
Exception: In an emergency situation, the time limit shall not apply where approved.
Blasting lead lines shall remain shunted (shorted) and shall not be connected to the blasting machine or other source of current until the blast is to be fired.
A permit shall be obtained from the local fire official and law enforcement officer of the jurisdiction for any outdoor exhibition of 1.1 G fireworks (UN0333), 1.2 G fireworks (UN0334), 1.3 G fireworks (UN0335), 1.4 G fireworks (UN0336), 1.4 G special effects fireworks (UN0432), 1.4 S fireworks (UN0337) and 1.4 S special effects fireworks (UN0432) fireworks and any indoor exhibition of 1.4 G special effects fireworks (UN0432), 1.4 S fireworks (UN0337) and 1.4 S special effects fireworks (UN0432) pursuant to the applicable provisions of section 3743.54 of the Revised Code. The permit shall bear the signatures of the fire official and law enforcement official having jurisdiction and the licensed exhibitor applying to conduct the fireworks exhibition. The permit shall identify the certified fire safety inspector, fire chief, or fire prevention officer who will be present before, during, and after the fireworks exhibition, where appropriate.
The orders to cease operations, postpone the fireworks exhibition and the revocation of the fireworks exhibition permit may be communicated verbally by the authority having jurisdiction. When so ordered or when the fireworks exhibition permit has been revoked, the exhibitor shall cease firing of the fireworks exhibition immediately.
Exception: Minor repairs to fuses shall be allowed. For electrically ignited exhibitions, attachment of electric matches and similar tasks shall be allowed.
Exception: For electrically fired fireworks exhibitions, or exhibitions where all shells are loaded into mortars prior to the show, there is no requirement for separation of shells according to size or their designation as salutes.
Exception: For electrically fired fireworks exhibitions, or exhibitions where all shells are loaded into mortars prior to the show, there is no requirement for separation of shells according to size, their designation as salutes, or for the use of ready boxes.
Before any flame effects exhibition permit issued under this rule is considered to be a valid permit to allow the licensed flame effects exhibitor to conduct a flame effects exhibition, the permit, upon approval, must be signed and dated by the local fire code official having jurisdiction. As required by the local fire code official to confirm compliance with this paragraph, receipt of the permit and/or any conditions associated thereto, the flame effects exhibitor shall sign and date the permit application, the permit and/or any other required documentation.
When a permit is required by this rule, a local fire code official shall be present during the production, exhibition, demonstration, or simulation using flame effects.
Exception: When issuing a permit for a group I or group II flame effects production, exhibition, demonstration, or simulation using flame effects, the local fire code official may determine that a local fire code official need not be present during such an exhibition.
If a permit is required by this rule, the permit shall identify the local fire code official who will be present before, during, and after the flame effects exhibition.
If any portion of the fire protection or life safety systems of a structure are interrupted during the operation of flame effects, a local fire code official must grant a prior approval of and be present during such interruptions.
Any performance adding flame effects different from the performance described in the permittee's plan shall require approval by the local fire code official having jurisdiction.
After a permit has been granted, the permittee shall keep the plan available at the site for safety inspectors or other designated agents of each authority having jurisdiction.
The local fire code official shall order the immediate cessation of the flame effects exhibition due to unsafe conditions or operations, unsafe spectator conditions, or any other condition in violation of this rule. The orders to cease operations, postpone the flame effects exhibition and the revocation of the flame effects exhibition permit may be communicated verbally by the local fire code official. When so ordered or when the flame effects exhibition permit has been revoked, the flame effects exhibitor shall cease the flame effects exhibition immediately. The flame effects exhibitor may reapply for a new permit for the flame effects exhibition when the local fire code official is satisfied that all rules, conditions, and operations are safe or have been complied with.
Quantities of flammable flame effect materials and devices in excess of those used in one day shall be permitted to be stored in holding areas with the approval of the local fire official.
Flammable flame effect materials and loaded devices in holding areas shall be secured or supervised continuously by an attendant trained in emergency response procedures.
All flame effects and flame effects exhibitors shall comply with NFPA 160 and the NFPA 160 annexes as listed in rule 1301:7-7-80 of the Administrative Code.
Exception:If approved by the state fire marshal, any licensed manufacturer of fireworks that possesses fireworks for sale and sells fireworks under division (C) of section 3743.04 of the Revised Code, or a designee of the manufacturer, whose identity is provided to the state fire marshal by the manufacturer, who serves as an instructor at a continuing education program outlined above shall not have to attend an additional continuing education program as a student during that same licensing year.
Exception:If approved by the state fire marshal, any licensed wholesaler of fireworks or a designee of the wholesaler, whose identity is provided to the state fire marshal by the wholesaler, who serves as an instructor at a continuing education program as outlined above shall not have to attend an additional continuing education program as a student during that same licensing year.
In accordance with Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 (2006 or 2017 edition as applicable per paragraph (A)(1)(C)(5601.1.3) of this rule) and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code, a licensed wholesaler may offer for sale and sell fireworks at wholesale or retail, and may conduct other fireworks related activities on its licensed premises, for only the following categories of fireworks: 1.1 G fireworks (UN0333), 1.2 G fireworks (UN0334), 1.3 G fireworks (UN0335), 1.4 G fireworks (UN0336), 1.4 G special effects fireworks (UN0431), 1.4 S fireworks (UN0337) or 1.4 S special effects fireworks (UN0432).
In accordance with Chapter 3743. of the Revised Code, including section 3743.27 of the Revised Code, paragraph (AA)(5627) this rule, and the applicable portions of NFPA 1124 as listed in rule 1301:7-7-80 of the Administrative Code, a licensed fountain device retailer may offer for sale and sell at retail 1.4 G fireworks (UN 0336) that meet the definition of a 'fountain device' as defined in division (H) of section 3743.01 of the Revised Code and this code.
All such shipments must be in accordance with federal laws, rules and regulations, Chapter 3743. of the Revised Code, this rule and the applicable provisions of NFPA 1123, NFPA 1124 and/or NFPA 1126 as listed in rule 1301:7-7-80 of the Administrative Code.
No other types of fireworks may be manufactured, sold, purchased, shipped, transported, possessed, ignited, displayed, stored or otherwise used in Ohio.
Exception:A permit for a fireworks exhibition may be transferred to a substitute licensed exhibitor as provided for in paragraph (H)(8)(g)(5608.8.7) of this rule.
Exception:This requirement does not apply to fireworks plants existing on or before August 3, 1931.
Exception:Any individual that is a valid Ohio licensed exhibitor of fireworks pursuant to the provisions of this rule who wishes to act as an employee of another properly licensed exhibitor is not required to be registered pursuant to this paragraph.
Exception:Semi-trailers which have been converted to a magazine approved for the storage of explosive materials.
A fireworks showroom structure that exists on July 1, 1997, shall be retrofitted on or before June 1, 1998, with interlinked fire detection, smoke exhaust, and smoke evacuation systems that are approved by the superintendent of the division of industrial compliance.
All retail sales of 1.4 G fireworks by a licensed manufacturer or wholesalers shall only occur from the inside of an approved retail sales showroom or a representative sample showroom, located on a licensed premises and from no other structure or device outside a licensed building.
"1.4 G fireworks."1.4 G fireworks, as that term is defined in the Revised Code and this code, that are purchased, handled, stored, possessed, used, or discharged by consumers pursuant to section 3743.27 or section 3743.45 of the Revised Code. This term includes consumer fireworks.
"1.4 G fireworks discharge site."The area where any 1.4 G firework is discharged including the point of discharge and the area immediately surrounding that point.
Consumer fireworks discharge incident.Any act or omission that occurs at a location where 1.4 G fireworks are purchased, possessed, handled, stored, used or discharged that results in injury or death or a substantial risk of injury or death to any person or results in property damage in excess of one thousand dollars and that involves either
"Discharge."Includes the use, explosion, detonation, ignition or any other discharge or use of 1.4 G fireworks in any manner.
"Fireworks establishment."Any fireworks manufacturer, wholesaler, retailer, or storage premise subject to licensure under Chapter 3743. of the Revised Code.
"Spectator."Any person other than a person who is directly engaged in the discharge of 1.4 G fireworks.
Exception to (iv) and (v):Quantity limits may be increased and separation distances may be decreased by the fire marshal for 1.4 G fireworks that are properly permitted in accordance with paragraph (E)(1)(a)(i)(a)(105.1.1.1.1) of rule 1301:7-7-01 of the Administrative Code and paragraph (A)(2)(5601.2) of this rule and stored in a magazine in accordance with paragraph (D)(5604) of this rule.
Exceptions:
Exception:Matches, lighters, or open flame devices to be specifically used to lawfully ignite 1.4 G fireworks for discharge purposes may be within the 1.4 G fireworks discharge site.
Exception:Items may, as authorized by a fire official or law enforcement official on site, be moved as necessary to prevent further injury or death to any member of the public or a threat of imminent fire or explosion.
"Fountain device."A specific type of 1.4 G firework that meets all of the following criteria:
"Fountain device retailer"or"licensed retailer."A person licensed pursuant to section 3743.26 of the Revised Code.
"Fountain device sales location." The approved building where licensed fountain device sales occur and any approved contiguous designated external fountain device storage areas on the same premise as the approved building.
"Retail sale" or "sell at retail." A sale of fireworks to a purchaser who intends to use the fireworks, and not resell them.
"CFRS facility."A consumer fireworks retail sales facility as define in NFPA 1124 as set forth in rule 1301:77-80 of the Administrative Code.
"Highly flammable materials."A "flammable gas," "flammable liquid," "flammable liquified gas," "flammable material," or" flammable solid" as defined in this code that are capable of being readily ignited from common sources of heat or similar causes. Examples of highly flammable materials include aerosols, acetone, rubbing alcohol, hand sanitizers, pool chemicals, automotive fluids, and other similar products, regardless of form or packaging, existing in a structure licensed for fountain device retail sales.
"Open for business."Having the intent and ability to engage in any lawful licensed fountain device retailer activity authorized by sections 3743.26 to 3743.29 of the Revised Code.
"Store."A store as define in NFPA 1124 as set forth in rule 1301:7-7-80 of the Administrative Code.
"Net explosive weight."
"Pyrotechnic composition."
Except as provided in divisions (C) and (D) of section 3737.26 of the Revised Code, a licensed retailer's license is effective for one year beginning on the first day of December and shall expire on the 30th day of November of the year after it was issued.
NO FIREWORKS DISCHARGE
WITHIN 300 FEET
All fountain device sales locations shall comply with the sections 5627.7.1 and 5627.7.2 of this rule.
Exception: A safety pamphlet does not have to be furnished to a purchaser who is a licensed retailer, licensed manufacturer, licensed wholesaler, or licensed exhibitor of fireworks in this state.
"Do not allow children to play with fireworks. Sparklers, a firework often considered by many to be the ideal "safe" device for children, burn at very high temperatures and should not be handled by children. Children may not understand the danger involved with fireworks and may not act appropriately while using the devices or in case of emergency.
Set off fireworks outdoors in a clear area, away from houses, dry leaves, or grass and other flammable materials.
Keep a bucket of water nearby for emergencies and for pouring on fireworks that fail to ignite or explode.
Do not try to relight or handle malfunctioning fireworks. Soak them with water and throw them away.
Be sure other people are out of range before lighting fireworks.
Never light fireworks in a container, especially a glass or metal container.
Keep unused fireworks away from firing areas.
Store fireworks in a cool, dry place.
Check instructions for special storage directions.
Observe state and local law.
Never have any portion of your body directly over a firework while lighting.
Do not experiment with homemade fireworks."
Exception: Safety glasses do not have to be made available for a purchaser who is a licensed retailer, licensed manufacturer, licensed wholesaler, or licensed exhibitor of fireworks in this state.
The state fire marshal may take any actions authorized by sections 3743.26 to 3743.29 of the Revised Code and this code to enforce any applicable laws and rules for fountain devices.
"Fee."The consumer fireworks (1.4 G Fireworks) sales fee established in division (B) of section 3743.22 of the Revised Code.
"Fee period."The period beginning on the first day of October and ending on the thirtieth day of the following September.
"Gross receipts."Excludes the amount of taxes a licensed retailer, licensed manufacturer, or licensed wholesaler collects from a consumer under Chapter 5739. of the Revised Code on behalf of the state or a political subdivision.
1301:7-7-56 88
Ohio Admin. Code 1301:7-7-56
Five Year Review (FYR) Dates: 12/15/2022
Promulgated Under: 119.03
Statutory Authority: 3737.22(A)(1) and (14), 3737.82, 3737.83, 3743.02(B)(3), 3743.04(F), (H), (K), 3743.05, 3743.15(B)(3), 3743.17(E), (H), (J), 3743.18(A), 3743.22(E), 3743.25(A)(2), 3743.28(A), 3743.451, 3743.53(A), (B), (E)(1); 3743.56, 3743.58, 3743.70(D)
Rule Amplifies: 3743.45, 3743.22(E), 3743.28(A), 3743.451, 3743.47, 3743.67, 3743.27; 3743.22; 3743.28, 3743.021, 3743.08, 3743.151, 3743.21, 3743.25, 3743.26, 3743.27, 3743.28, 3743.29, 3743.44, 3743.70.
Prior Effective Dates: 07/01/1979, 06/01/1985, 06/15/1992, 07/01/1993, 09/01/1995, 03/30/1998, 09/01/2005, 07/01/2007, 11/01/2011, 12/15/2017, 01/05/2019, 07/03/2022