Table 4. Maximum Allowable Rates of Emission of Particulate Matter from New Fuel Burning Equipment | |||
Heat Input (H) | Allowable Emission Rate (E) | Heat Input (H) | Allowable Emission Rate (E) |
106 Btu/hr | lb/106 Btu | joules/hr | nanogram/joule |
10 or less | 0.600 | 1.05 x 1010 | 258 |
20 | 0.548 | 2.11 x 10 10 | 235 |
30 | 0.519 | 3.16 x 1010 | 224 |
40 | 0.500 | 4.22 x 1010 | 215 |
50 | 0.486 | 5.27 x 1001 | 209 |
100 | 0.444 | 1.05 x 1011 | 191 |
150 | 0.421 | 1.58 x 1011 | 181 |
200 | 0.405 | 2.11 x 10 11 | 174 |
250 | 0.394 | 2.64 x 1011 | 169 |
Interpolation and extrapolation of the data in this table shall be accomplished by the use of equations:
E = 0.811 H -0.131 (English units)
E = 5,307 H -0.131 (Metric units)
where E = allowable emission rate in lb/million Btu of heat input [nanogram/joule] and H = heat input in millions of Btu/hr [joules/hr].
N.D. Admin Code 33.1-15-05-02
General Authority: NDCC 23.1-06-04; S.L. 2017, ch. 199, § 1
Law Implemented: NDCC 23.1-06-04, 23.1-06-13; S.L. 2017, ch. 199, § 21