Section 14J .1527 - PROTECTION EQUIPMENT FOR ELECTRICAL LIGHTS
(a) Each facility shall adequately protect electric lights in cells from damage by inmates.
(b) Fittings shall be either covered with 3/8 inch tempered lenses for diffusing light or protected with steel wire.
(c) Steel plate brackets shall be provided for mounting light receptacles.