Section 1001.34 - Exhibit 34: electric interconnectionExhibit 34 shall contain:
A detailed description of the proposed electric interconnection including:
(a) the design voltage and voltage of initial operation;(b) the type, size, number and materials of conductors;(c) the insulator design;(d) the length of the transmission line;(e) the typical dimensions and construction materials of the towers;(f) the design standards for each type of tower and tower foundation;(g) for underground construction, the type of cable system to be used and the design standards for that system;(h) for underground construction, indicate on a profile of the line the depth of the cable and the location of any oil pumping stations and manholes;(i) equipment to be installed in any proposed switching station or substation including an explanation of the necessity for any such switching station or substation;(j) any terminal facility; and(k) the need for cathodic protection measures.N.Y. Comp. Codes R. & Regs. Tit. 16 § 1001.34