Section 1001.34 - Exhibit 34: electric interconnection

Exhibit 34 shall contain:

A detailed description of the proposed electric interconnection including:

(a) the design voltage and voltage of initial operation;
(b) the type, size, number and materials of conductors;
(c) the insulator design;
(d) the length of the transmission line;
(e) the typical dimensions and construction materials of the towers;
(f) the design standards for each type of tower and tower foundation;
(g) for underground construction, the type of cable system to be used and the design standards for that system;
(h) for underground construction, indicate on a profile of the line the depth of the cable and the location of any oil pumping stations and manholes;
(i) equipment to be installed in any proposed switching station or substation including an explanation of the necessity for any such switching station or substation;
(j) any terminal facility; and
(k) the need for cathodic protection measures.