Section 8.321.11.48 - HAZARDOUS AREASA. Hazardous areas include the following:(1) fuel fired equipment rooms;(2) bulk laundries or laundry rooms with more than 100 sq. ft.;(3) storage rooms with more than 50 sq. ft. but less than 100 sq. ft. not storing combustibles;(4) storage rooms with more than 100 sq. ft. storing combustibles;(5) chemical storage rooms with more than 50 sq. ft.; and(6) garages, maintenance shops, or maintenance rooms.B. Hazardous areas on the same floor or abutting a primary means of escape or a sleeping room shall be protected by either: (1) an enclosure of at least one-hour fire rating with self-closing or automatic closing on smoke detection fire doors having a three-quarter hour rating; or(2) an automatic fire protection (sprinkler) and separation of hazardous area with self-closing doors or doors with automatic-closing on smoke detection; or(3) any other hazardous areas shall be enclosed with walls with at least a 20 minute fire rating and doors equivalent to one and three-quarter inches solid bonded wood core, operated by self-closures or automatic closing on smoke detection.C. All boiler, furnace or fuel fired water heater rooms shall be protected from other parts of the building by construction having a fire resistance rating of not less than one hour. Doors to these rooms shall be one and three-quarter inches solid core.N.M. Admin. Code § 8.321.11.48