N.J. Admin. Code § 5:70-4.8

Current through Register Vol. 56, No. 21, November 4, 2024
Section 5:70-4.8 - Standpipe system
(a) All buildings having floors used for human occupancy located more than six stories above grade shall be equipped with wet standpipes. Standpipes shall be located and installed in accordance with the New Jersey Uniform Construction Code except as follows:
1. Standpipes shall be capable of accepting a delivery by fire department apparatus of a minimum of 250 gpm at 65 psi to the topmost remote standpipe outlet in buildings equipped throughout with an automatic fire suppression system or a minimum of 500 gpm at 65 psi to the topmost remote standpipe outlet in all other buildings.
2. Hose and hose cabinets shall not be required.

N.J. Admin. Code § 5:70-4.8